- 10 -

(1) P (proportional action)

Control output rate (%) is set for measuring range.
Control output value changes in proportion with measured
value (PV) and set value (SV).
For wide proportional band, change of control output is small
relative to deviation.  The narrower the proportional band is,
the larger the output variation is and the more intense
proportional action is.  Too narrow proportional band causes
ON-OFF like action with oscillation. 

(2) I (integral time)

A function that compensates the offset created by
proportional action.  Effect of compensation is weaker for
longer integral time and is intensified by shortening time.
Too short integral time causes integrating hunting and may
result in wavy operation.

(3) D (derivative time)

Improves stability of control by reducing overshooting of
integration from expected change of the control output.
Effect of compensation is weaker for shorter derivative time
and is intensified for longer time.  Too long derivative time
may result in oscillating operation.

6-3. Control output characteristics (

digit of function

selecting screen of mode 2 screen group)

Control output characteristics determines the control output
direction according to the measured value (PV) relative to the set
value (SV).

(1)

(RA characteristics)

Control output increases for lower measured value relative to
set value, it is used for heating on temperature control.

(2)

(DA characteristics)

Control output decreases for lower measured value relative to
set value, it is used for cooling on temperature control.

6-4. Error message

(1) Defect of measuring input

In case of thermocouple break, R.T.D.  A break
and PV being approx. 10% greater than higher
limit of measuring range.

In case of PV being approx. 10% less than the
lower limit of measuring range with inverted
polarity of input wiring.

Cold junction (CJ) defect to higher side for
thermocouple input.

Cold junction (CJ) defect to lower side for
thermocouple input.

Break of B or B and multiple break of A, B, B
upon R.T.D. input

(2) Defect of Heater Break Alarm CT Input

The CT input value exceeds 55A (550A for 0~5V
DC input). 

The CT input value falls to -5A (-50A for 0~5V
DC input) or lower.

7. Instructions on Communication

7-1. General

Section 7 deals with communication interface, which is an
optional function, and communication procedure. 

For the SR73A and 74A series, two types of communication
interface, RS-422A and RS-485 are available.  Each enables a
personal computer or the like to set and read various data by the
use of signals which conform with EIA standards.

RS-422A and RS-485 are communication standards established
by the Electric Industries Association (EIA), which are meant for
electrical or mechanical matters, the so-called hardware, but not
for the software portion of the data transmission procedure.

Accordingly, communication even with an apparatus having the
same interface cannot be made unconditionally.  It requires a
thorough understanding of specifications and procedures. 

The use of RS-422A or RS-485 allows a plurality of apparatuses
to be connected in a parallel configuration.  It is also possible to
use a line converter for conversion of RS-232C to/from RS-422A
and RS-232C to/from RS-485. 

7-2. How to connect SR73A or 74A with host computer 

7-2-1. Control signals

Since the apparatus is provided with input/output transmitting and
receiving data lines and an earthing line for signals but not with
any other signal line, control signals should be processed by the
host side.

The method of processing differs from system to system and
connection details should meet requirements of the host
computer. Examples of connection are shown in the following. 

7-2-2. Connection of RS-422A

(1) The logical levels of input and output of this apparatus are

basically as follows: 
Mark state

**– <**+ (Example: SD- < SD+)

(including the state in which communication is not carried
out)
Space state

**– >**+ (Example: SD- > SD+)

However, since the impedance of SD+ and SD- of this
apparatus is high until just before transmission, the above
levels are output just before commencing transmission. 

(2) Example of Connection of RS-422A

Note:

Message of heater break alarm is only displayed on
heater break alarm set screen.

is shown when output is OFF.  It is not

defective.

Note:

Contact to us or our representative in case of any defect
regarding this product.

SD
SD 
RD
RD
SG

+

-

+

-

+

-

+

-

+

-

+

-

SD
SD
RD
RD
SG

2
3
4
5
1

terminal No.

SD
SD
RD
RD
SG

2
3
4
5
1

Host computer 

Shielding wire

Transmitted data

Received data

Earthing for signal

Transmitted data

Received data

Earthing for signal

FG (Earthing for protection)

Terminal resistance (510

)

SR73A and 74A Controllers 1

terminal No.

SR73A and 74A Controllers 2

Note:

Some line converters between RS-232C and RS-422A
may have the following indication for terminal
(connector) output.  If that is the case, logical levels
should be checked before connection.

Содержание SR73A Series

Страница 1: ...o the instrument On the terminal nameplate affixed to the case of your instrument the mark is printed This is to warn you of the risk of electrical shock which may result if the charger is touched while it is energized A means to allow the power to be turned off such as a switch or a breaker should be installed in the external power circuit to be connected to the power terminal of the instrument F...

Страница 2: ... 14 8 Specifications 15 4 1 Introduction 1 1 Check before use This product has been fully checked for quality assurance prior to shipment Nevertheless you are requested to make sure that there is no error damage or shortage of delivered items by confirming the model codes and checking the external view of the product and the number of accessories Confirmation of Model Codes Check the model codes s...

Страница 3: ...th 48 height 91 6 width 44 6 Dimension of current transformer CT for heater break alarm For 0 30A CTL 6 S For 0 50A CTL 12 S36 8 unit mm 2 5 Wiring 1 Wiring operation should be done according to the instruction for the terminal arrangement in section 2 6 Exercise care that no wrong connection is made 2 Crimp terminal should accommodate the M3 5 screw and should have a width of less than 7mm 3 For ...

Страница 4: ...nitor LED green On selection by ON turns on AT waiting key flashes on AT execution 3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON 5 MAN manual control output monitor LED green Flashes when control output is in manual operation 6 STBY control output stop monitor LED green Tu...

Страница 5: ... decimal point in the rightmost position on the top row flashes Press the or key to change the lower limit value and press the key to register the data Upon registering the lower limit value data the decimal point in the rightmost digit in the bottom row begins to flash Change the higher limit value by pressing the or key and register it by means of the key Upon registering the higher limit value ...

Страница 6: ...ualoperation 0 100 Themeasuredvalue PV isdisplayedonthetopandthecontroloutput valueonthebottom PressingtheMANkeyonthisscreenswitches autotomanualandviceversa RefertoItem4 6 1 fordetail Control execution stop selecting screen Initialvalue EXEC Settingrange EXEC STBY Execution orstop ofcontrolisselected RefertoItem4 6 2 fordetail AT auto tuning action control screen Initialvalue OFF Settingrange OFF...

Страница 7: ...ockissetonlockNo 1 2or3 noselectioncanbeperformedevenifthedigitpointis flashing Digits and arenotshownincaseofnooption Digitsof and arenotdisplayed Measuring range code select digit Initialvalue Multi05 Voltage V 81 Current95fixed Selectingtwodigitsfrom 4 5 Measuringrangecodetable Control output characteristic select digit Initialvalue RA heatingcharacteristics DA coolingcharacteristics RefertoIte...

Страница 8: ...the higher limit value is forced to be the lower limit value 1 Therefore the higher limit value cannot be set to be less than the lower limit value 1 ENT Note Moving to another screen while maintaining the manual mode is possible In this case it should be noted that control output is made manually The apparatus is in the manual mode when the MAN monitor LED is flashing ENT 6 1 14 Soft Start Time S...

Страница 9: ...m option is added and the lower limit alarm of the alarm type select digit on the function selecting screen of the mode 2 group screen group is selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the lower limit of the measuring range the action point is low...

Страница 10: ...nd 74A series two types of communication interface RS 422A and RS 485 are available Each enables a personal computer or the like to set and read various data by the use of signals which conform with EIA standards RS 422A and RS 485 are communication standards established by the Electric Industries Association EIA which are meant for electrical or mechanical matters the so called hardware but not f...

Страница 11: ...ront panel turns on and the commands for read and write through communication become valid Front key operation works only to change from remote to local 7 3 2 Communication address setting screen RS 422A and RS 485 allow connection of a plurality of apparatuses but in fact communication is carried out between two apparatuses Therefore the address of each apparatus is designated by a number between...

Страница 12: ... value including a code is less than six characters 0 is inserted between the code and the figure or figures to make the value six characters When a code is excluded each of the 5 characters is a figure or a decimal point Examples of numerical data 1 Command The text format of read data contains only of a command of two characters Command Contents of Read Data PV value Execution SV value 1 Control...

Страница 13: ...No did not match The end character was not CR 0DH A hardware error such as a framing error overrun or a parity error occurred 7 5 5 Restrictions by commands etc 1 Restrictions by Read Command Upon receiving the D1 read command the status of unequipped options AH AL HB SB become 0 30H 2 Restrictions by Write Command In the case of P OFF and Y and P output write data of E2 write command of manual ou...

Страница 14: ...xt Data 3AH BCC CR 0DH Higher position Lower position Higher position Lower position Received data Transmitted data D1 D1 STBY MAN AH AL AT SB 0 30H or 1 31H PV value SV value Output value Received data Transmitted data D2 D2 Set value of AH Set value of AL Received data Transmitted data D3 D3 CT current value Set value of HB Received data Transmitted data D4 D4 Set value of SB Received data Trans...

Страница 15: ... Sampling cycle 0 5 sec PV bias range 200 unit PV filter 0 100 sec 0 without filter Control Control mode Auto tuning PID ON OFF control Proportional band P Off 0 1 999 9 FS Off setting On Off action Integral time I Off 1 6000 sec Off setting P PD action Derivative time D Off 1 3600 sec Off setting P PI action Manual reset MR 50 0 50 0 Valid when P OFF and I OFF Output limiter Lower limit limiter 0...

Страница 16: ...tact type or the SSR drive voltage type Alarm action Heater amperage detected by externally attached CT except 0 5V DC input Alarm output On upon detection of heater break while control output is On Current setting range Off 0 1 50 0A Alarm action stops when Off is set or Off 1 500A when 0 5 V DC for CT input is selected Setting resolution 0 1A or 1A Amperage display 0 0 55 0A or 0 550A Display ac...

Отзывы: