background image

- 9 -

(2) Abort of AT

To abort the AT action, by showing the AT action control
screen, press the        or        key to select            and press

key to abort AT and LED for AT monitoring also goes

off.

(3) AT unable for following conditions.

• When the control stop mode is on (The AT screen is not

displayed.) 

• During manual output control (The AT screen is not

displayed.)

• The proportional band is             setting (ON/OFF action).

(The AT screen is not displayed.)

• Lock No.2 or 3 is selected on the key lock set screen.
• PV (measured) value is over the scale.
• During the execution of soft start 

(4) AT is automatically canceled in the following condition

during AT execution.
• Duration equal to or longer than 2 hours passed in the

output level of 0% or 100%.

• Power shutdown.
• PV (measured) value is over the scale during AT

execution.

(5) The items enable to be set are as follows:

• Level setting of the higher limit alarm.
• Level setting of the lower limit alarm or heater break

alarm.

• Screen number setting and key lock setting on the direct

call screen of mode 1 screen group.

(6) Relationship between AT and set value bias is as follows;

• When SB terminal is shorted before AT execution, AT

executes in the condition with SV+set value bias.  

• When SB terminal is opened during AT execution

mentioned in the above, AT  executes with SV+set value
bias condition, then controlled with SV condition after
completing AT execution.

• When SB terminal is opened, AT executes with SV

condition.

• When SB terminal is shorted during AT execution

mentioned in the above, AT executes with SV condition,
then controlled with SV+set value bias condition after
completing AT execution.

5-3. Setting of alarm

(1) Higher limit alarm setting

• The higher limit alarm set screen is shown in case where

alarm option is added and the higher limit alarm of the
alarm type select digit on the function selecting screen of
the mode 2 screen group is selected.

• Higher limit deviation value alarm is output for measured

value to be greater than set value + alarm set value.

• For higher limit deviation value alarm, if set value + alarm

set value exceeds the higher limit of the measuring range,
the action point is the higher limit of the measuring range.

• Higher limit absolute value alarm outputs alarm signal for

the measured value exceeds the alarm set value.

• With the        or        key, value at which the alarm signal

should be output is selected and registered with        key.

Example 1:
In case of setting the alarm action point at 600 °C for higher
limit deviation value alarm.  Set value is 500 °C.
As 500 °C + X °C + = 600 °C, X=600-500 = 100 °C should
be set.

Example 2:
In case of setting the alarm action point at 600 °C for higher
limit absolute value alarm.
The set point is action point.

(2) Lower limit alarm setting

• The lower limit alarm set screen is shown in case where

alarm option is added and the lower limit alarm of the
alarm type select digit on the function selecting screen of
the mode 2 group screen group is selected.

• Lower limit deviation value alarm is output for measured

value to be less than set value + (alarm set value).

• For lower limit deviation value alarm, if set value + (alarm

set value) is less than the lower limit of the measuring
range, the action point is lower limit of the measuring
range.

• Lower limit absolute value alarm outputs alarm signal for

the measured value is less than the alarm set value.

• With the        or        key, value at which the alarm signal

should be output is selected and registered with        key.

(3) Heater break alarm setting

• The heater break alarm value setting screen is displayed

when the apparatus is equipped with the optional heater
break alarm function and heater break alarm is selected in
the alarm type selection digit of the function selecting
screen of the mode 2 screen group.  The top row shows for
monitoring purposes the value of the presently flowing
current detected by CT and the bottom row shows the set
value of the alarm current.

• When OFF is set as the heater break alarm value, the

heater break alarm does not function.

• By setting OFF during heater break alarm signal output,

heater break alarm output is terminated.

• For set value other than OFF, heater break alarm signal is

output if the current that flows in case where control
output (contact or SSR drive voltage) is ON, is less than
set value.

• If LOCK mode is selected at heater break alarm action

mode select digit on the function selecting screen of the
mode 2 screen group and the break alarm signal is output,
alarm signal is only terminated by changing the break
alarm value into OFF or shutting down power.
If REAL mode is selected and heater current is less than
current value being set, break alarm signal is generated.  If
heater current exceeds the current threshold (0.1A), output
of break alarm is terminated.

• Set the heater break alarm current value by means of the of

the        or        key and register it by using the        key.

6.  Supplement

6-1.  Auto return function

In case there is no key operation for three minutes on each of the
screens except the control output screen and the heater break
alarm value setting screen, the basic screen of the mode 0 screen
group is displayed (auto return).

6-2. PID (Screen No.2, 4 and 5 of mode 1 screen group)

PID values are automatically set by performing auto tuning,
modification may be required for object to be controlled.
If auto tuning is not performed, PID value should be set.  

Note:

When the AT action is aborted, each value for PID is not
changed.

ENT

ENT

key

ENT

key

key

one by one

point flashing

point flashing

point goes off to 
indicate registration

0-2 Higher limit deviation value alarm set screen  

continuing

key

ENT

key

key

one by one

point flashing

point flashing

point goes off to 
indicate registration

0-2 Higher limit deviation value alarm set screen  

continuing

ENT

ENT

Содержание SR73A Series

Страница 1: ...o the instrument On the terminal nameplate affixed to the case of your instrument the mark is printed This is to warn you of the risk of electrical shock which may result if the charger is touched while it is energized A means to allow the power to be turned off such as a switch or a breaker should be installed in the external power circuit to be connected to the power terminal of the instrument F...

Страница 2: ... 14 8 Specifications 15 4 1 Introduction 1 1 Check before use This product has been fully checked for quality assurance prior to shipment Nevertheless you are requested to make sure that there is no error damage or shortage of delivered items by confirming the model codes and checking the external view of the product and the number of accessories Confirmation of Model Codes Check the model codes s...

Страница 3: ...th 48 height 91 6 width 44 6 Dimension of current transformer CT for heater break alarm For 0 30A CTL 6 S For 0 50A CTL 12 S36 8 unit mm 2 5 Wiring 1 Wiring operation should be done according to the instruction for the terminal arrangement in section 2 6 Exercise care that no wrong connection is made 2 Crimp terminal should accommodate the M3 5 screw and should have a width of less than 7mm 3 For ...

Страница 4: ...nitor LED green On selection by ON turns on AT waiting key flashes on AT execution 3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON 5 MAN manual control output monitor LED green Flashes when control output is in manual operation 6 STBY control output stop monitor LED green Tu...

Страница 5: ... decimal point in the rightmost position on the top row flashes Press the or key to change the lower limit value and press the key to register the data Upon registering the lower limit value data the decimal point in the rightmost digit in the bottom row begins to flash Change the higher limit value by pressing the or key and register it by means of the key Upon registering the higher limit value ...

Страница 6: ...ualoperation 0 100 Themeasuredvalue PV isdisplayedonthetopandthecontroloutput valueonthebottom PressingtheMANkeyonthisscreenswitches autotomanualandviceversa RefertoItem4 6 1 fordetail Control execution stop selecting screen Initialvalue EXEC Settingrange EXEC STBY Execution orstop ofcontrolisselected RefertoItem4 6 2 fordetail AT auto tuning action control screen Initialvalue OFF Settingrange OFF...

Страница 7: ...ockissetonlockNo 1 2or3 noselectioncanbeperformedevenifthedigitpointis flashing Digits and arenotshownincaseofnooption Digitsof and arenotdisplayed Measuring range code select digit Initialvalue Multi05 Voltage V 81 Current95fixed Selectingtwodigitsfrom 4 5 Measuringrangecodetable Control output characteristic select digit Initialvalue RA heatingcharacteristics DA coolingcharacteristics RefertoIte...

Страница 8: ...the higher limit value is forced to be the lower limit value 1 Therefore the higher limit value cannot be set to be less than the lower limit value 1 ENT Note Moving to another screen while maintaining the manual mode is possible In this case it should be noted that control output is made manually The apparatus is in the manual mode when the MAN monitor LED is flashing ENT 6 1 14 Soft Start Time S...

Страница 9: ...m option is added and the lower limit alarm of the alarm type select digit on the function selecting screen of the mode 2 group screen group is selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the lower limit of the measuring range the action point is low...

Страница 10: ...nd 74A series two types of communication interface RS 422A and RS 485 are available Each enables a personal computer or the like to set and read various data by the use of signals which conform with EIA standards RS 422A and RS 485 are communication standards established by the Electric Industries Association EIA which are meant for electrical or mechanical matters the so called hardware but not f...

Страница 11: ...ront panel turns on and the commands for read and write through communication become valid Front key operation works only to change from remote to local 7 3 2 Communication address setting screen RS 422A and RS 485 allow connection of a plurality of apparatuses but in fact communication is carried out between two apparatuses Therefore the address of each apparatus is designated by a number between...

Страница 12: ... value including a code is less than six characters 0 is inserted between the code and the figure or figures to make the value six characters When a code is excluded each of the 5 characters is a figure or a decimal point Examples of numerical data 1 Command The text format of read data contains only of a command of two characters Command Contents of Read Data PV value Execution SV value 1 Control...

Страница 13: ...No did not match The end character was not CR 0DH A hardware error such as a framing error overrun or a parity error occurred 7 5 5 Restrictions by commands etc 1 Restrictions by Read Command Upon receiving the D1 read command the status of unequipped options AH AL HB SB become 0 30H 2 Restrictions by Write Command In the case of P OFF and Y and P output write data of E2 write command of manual ou...

Страница 14: ...xt Data 3AH BCC CR 0DH Higher position Lower position Higher position Lower position Received data Transmitted data D1 D1 STBY MAN AH AL AT SB 0 30H or 1 31H PV value SV value Output value Received data Transmitted data D2 D2 Set value of AH Set value of AL Received data Transmitted data D3 D3 CT current value Set value of HB Received data Transmitted data D4 D4 Set value of SB Received data Trans...

Страница 15: ... Sampling cycle 0 5 sec PV bias range 200 unit PV filter 0 100 sec 0 without filter Control Control mode Auto tuning PID ON OFF control Proportional band P Off 0 1 999 9 FS Off setting On Off action Integral time I Off 1 6000 sec Off setting P PD action Derivative time D Off 1 3600 sec Off setting P PI action Manual reset MR 50 0 50 0 Valid when P OFF and I OFF Output limiter Lower limit limiter 0...

Страница 16: ...tact type or the SSR drive voltage type Alarm action Heater amperage detected by externally attached CT except 0 5V DC input Alarm output On upon detection of heater break while control output is On Current setting range Off 0 1 50 0A Alarm action stops when Off is set or Off 1 500A when 0 5 V DC for CT input is selected Setting resolution 0 1A or 1A Amperage display 0 0 55 0A or 0 550A Display ac...

Отзывы: