- 1 -

"Notice"

Please ensure that this instruction manual is given to the final user
of the instrument.

Preface

This instruction manual is meant for those who will be involved
in the wiring, installation, operation and routine maintenance of
the SR73A and 74A series.
This manual describes the care, installation, wiring, function, and
proper procedures for the operation of SR73A and 74A series.
Keep this manual at the work site during operation of the SR73A
and 74A series.  While using this instrument, you should always
follow the guidance provided herein. 

For matters regarding safety, potential damage to equipment
and/or facilities, additional instructions are indicated by the
following headings: 

Exercise extreme caution as indicated.  This heading indicates
hazardous conditions that could cause injury or death of
personnel.

Exercise extreme caution as indicated.  This heading indicates
hazardous conditions that could cause damage to equipment
and/or facilities.

NOTE

This heading indicates additional instructions and/or notes.

The mark        designates a protective conductor terminal.  Make
sure to properly ground it.

The Matters regarding Safety

SR73A and 74A Series

Digital Controller

Instruction Manual

Thank you for purchasing the Shimaden SR73A and 74A Series.  Please check that the delivered product is
the correct item you ordered.  Please do not begin operating this product until you have read this instruction
manual thoroughly and understand its contents.

WARNING

CAUTION

SR73A and 74A series controllers are designed for controlling
temperature, humidity and other physical subjects.  It must not
be used in any way that may adversely affect the safety, health
or working conditions of those who come into contact with the
effects of its usage.  When used, adequate and effective safety
countermeasures must be provided at all times.  No warranty,
express or implied, is valid in the case of usage without having
implemented proper safety countermeasures.

WARNING

To avoid damage to the connected equipment, facilities or the
product itself due to a fault of the product, safety
countermeasure must be taken before usage, such as proper
installation of the fuse and the overheating protection device.
No warranty, express or implied, is valid in the case of usage
without having implemented proper safety countermeasures.

CAUTION

• The       mark on the plate affixed to the instrument:

On the terminal nameplate affixed to the case of your
instrument, the       mark is printed.  This is to warn you of the
risk of electrical shock which may result if the charger is
touched while it is energized.

• A means to allow the power to be turned off, such as a switch

or a breaker, should be installed in the external power circuit
to be connected to the power terminal of the instrument.
Fix the switch or the breaker adjacently to the instrument in a
position which allows it to be operated with ease, and with an
indication that it is a means of turning the power off.  The
switch or the breaker should meet the requirements of IEC
947.

• Fuse:

Since the instrument does not have a built-in fuse, do not
forget to install a fuse in the power circuit to be connected to
the power terminal.
The fuse should be positioned between the switch or the
breaker and the instrument and be attached to the L side of
the power terminal.

Fuse Rating: 250V AC 0.5A/medium lagged or lagged type 
Use a fuse which meets the requirements of IEC 127.

• Voltage/current of a load to be connected to the output

terminal and the alarm terminal should be within a rated
range.  Otherwise, the temperature will rise and reduce the
life of the product and/or result in problems with the product.
For the rated voltage/current, see 8. Specifications on page
15.  The output terminal should be connected with a device
which meets the requirements of IEC 1010.

• A voltage/current different from that of the input

specification should not be added on the input terminal.  It
may reduce the life of the product and/or result in problems
with the product. 
For the rated voltage/current, see 8. Specifications on page
15.
For the rated voltage (mV or V) or current (4~20 mA) input,
the input terminal should be connected with a device which
meets the requirements of IEC1010 as input terminals.

• In the case where the heater break alarm (optional) input is

0~5V DC, the CT input terminal should be connected to an
apparatus which meets IEC 1010 requirements. 

• As the CT input terminal for the heater break alarm

(optional), only the attachment CT should be used.  Using
anything else may result in problems with the product. 
For the CT provided, refer to 1-1 Check before Use on page
2. (Except when 0~5V DC input has been selected.)

• The SR73A and 74A series controllers are provided with a

draft hole for heat discharge.  Take care to prevent metal or
other foreign matter from obstructing it.  Failure to do so may
result in problems with the product and may even result in
fire.

CAUTION

SR73AFC-1DE  Sep. 2000

Содержание SR73A Series

Страница 1: ...o the instrument On the terminal nameplate affixed to the case of your instrument the mark is printed This is to warn you of the risk of electrical shock which may result if the charger is touched while it is energized A means to allow the power to be turned off such as a switch or a breaker should be installed in the external power circuit to be connected to the power terminal of the instrument F...

Страница 2: ... 14 8 Specifications 15 4 1 Introduction 1 1 Check before use This product has been fully checked for quality assurance prior to shipment Nevertheless you are requested to make sure that there is no error damage or shortage of delivered items by confirming the model codes and checking the external view of the product and the number of accessories Confirmation of Model Codes Check the model codes s...

Страница 3: ...th 48 height 91 6 width 44 6 Dimension of current transformer CT for heater break alarm For 0 30A CTL 6 S For 0 50A CTL 12 S36 8 unit mm 2 5 Wiring 1 Wiring operation should be done according to the instruction for the terminal arrangement in section 2 6 Exercise care that no wrong connection is made 2 Crimp terminal should accommodate the M3 5 screw and should have a width of less than 7mm 3 For ...

Страница 4: ...nitor LED green On selection by ON turns on AT waiting key flashes on AT execution 3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON 5 MAN manual control output monitor LED green Flashes when control output is in manual operation 6 STBY control output stop monitor LED green Tu...

Страница 5: ... decimal point in the rightmost position on the top row flashes Press the or key to change the lower limit value and press the key to register the data Upon registering the lower limit value data the decimal point in the rightmost digit in the bottom row begins to flash Change the higher limit value by pressing the or key and register it by means of the key Upon registering the higher limit value ...

Страница 6: ...ualoperation 0 100 Themeasuredvalue PV isdisplayedonthetopandthecontroloutput valueonthebottom PressingtheMANkeyonthisscreenswitches autotomanualandviceversa RefertoItem4 6 1 fordetail Control execution stop selecting screen Initialvalue EXEC Settingrange EXEC STBY Execution orstop ofcontrolisselected RefertoItem4 6 2 fordetail AT auto tuning action control screen Initialvalue OFF Settingrange OFF...

Страница 7: ...ockissetonlockNo 1 2or3 noselectioncanbeperformedevenifthedigitpointis flashing Digits and arenotshownincaseofnooption Digitsof and arenotdisplayed Measuring range code select digit Initialvalue Multi05 Voltage V 81 Current95fixed Selectingtwodigitsfrom 4 5 Measuringrangecodetable Control output characteristic select digit Initialvalue RA heatingcharacteristics DA coolingcharacteristics RefertoIte...

Страница 8: ...the higher limit value is forced to be the lower limit value 1 Therefore the higher limit value cannot be set to be less than the lower limit value 1 ENT Note Moving to another screen while maintaining the manual mode is possible In this case it should be noted that control output is made manually The apparatus is in the manual mode when the MAN monitor LED is flashing ENT 6 1 14 Soft Start Time S...

Страница 9: ...m option is added and the lower limit alarm of the alarm type select digit on the function selecting screen of the mode 2 group screen group is selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the lower limit of the measuring range the action point is low...

Страница 10: ...nd 74A series two types of communication interface RS 422A and RS 485 are available Each enables a personal computer or the like to set and read various data by the use of signals which conform with EIA standards RS 422A and RS 485 are communication standards established by the Electric Industries Association EIA which are meant for electrical or mechanical matters the so called hardware but not f...

Страница 11: ...ront panel turns on and the commands for read and write through communication become valid Front key operation works only to change from remote to local 7 3 2 Communication address setting screen RS 422A and RS 485 allow connection of a plurality of apparatuses but in fact communication is carried out between two apparatuses Therefore the address of each apparatus is designated by a number between...

Страница 12: ... value including a code is less than six characters 0 is inserted between the code and the figure or figures to make the value six characters When a code is excluded each of the 5 characters is a figure or a decimal point Examples of numerical data 1 Command The text format of read data contains only of a command of two characters Command Contents of Read Data PV value Execution SV value 1 Control...

Страница 13: ...No did not match The end character was not CR 0DH A hardware error such as a framing error overrun or a parity error occurred 7 5 5 Restrictions by commands etc 1 Restrictions by Read Command Upon receiving the D1 read command the status of unequipped options AH AL HB SB become 0 30H 2 Restrictions by Write Command In the case of P OFF and Y and P output write data of E2 write command of manual ou...

Страница 14: ...xt Data 3AH BCC CR 0DH Higher position Lower position Higher position Lower position Received data Transmitted data D1 D1 STBY MAN AH AL AT SB 0 30H or 1 31H PV value SV value Output value Received data Transmitted data D2 D2 Set value of AH Set value of AL Received data Transmitted data D3 D3 CT current value Set value of HB Received data Transmitted data D4 D4 Set value of SB Received data Trans...

Страница 15: ... Sampling cycle 0 5 sec PV bias range 200 unit PV filter 0 100 sec 0 without filter Control Control mode Auto tuning PID ON OFF control Proportional band P Off 0 1 999 9 FS Off setting On Off action Integral time I Off 1 6000 sec Off setting P PD action Derivative time D Off 1 3600 sec Off setting P PI action Manual reset MR 50 0 50 0 Valid when P OFF and I OFF Output limiter Lower limit limiter 0...

Страница 16: ...tact type or the SSR drive voltage type Alarm action Heater amperage detected by externally attached CT except 0 5V DC input Alarm output On upon detection of heater break while control output is On Current setting range Off 0 1 50 0A Alarm action stops when Off is set or Off 1 500A when 0 5 V DC for CT input is selected Setting resolution 0 1A or 1A Amperage display 0 0 55 0A or 0 550A Display ac...