background image

MSD16A-E01-A 

May. 2006 

Digital Indicator

 

SD16A Series

 

Instruction Manual

 

 

Please ensure that this instruction manual is given to the final user of the 
instrument.

 

Preface 

Thank you for purchasing Shimaden products.

 

Please check that the delivered product is the correct item that you 
ordered.

 

This instruction manual is meant for those who will be involved in the wiring, 
installation, operation and routine maintenance of the SD16A series, and 
describes about cautions, mounting, wiring, functions, and operation.

 

Please observe the contents, and always keep the manual close at hand 
when handling this instrument.

 

The following headings give a description of matters requiring user 
attention concerning safety, damage to machines and equipment, 
additional explanations and commentaries are described under the 
following headings.

 

WARNING 

Items concerning matters that may lead to 
an accident producing human injury or 
death, if the warning is not observed.

 

CAUTION 

Items concerning matters that may lead to 
an accident producing damage to machines 
or equipment, if the caution is neglected.

 

 

Note 

Note

 

Additional explanations and commentaries.

 

 

Contents 

Preface..................................................................................................... 1

 

Contents................................................................................................... 1

 

Safety Cautions........................................................................................ 1

 

1. Introduction .......................................................................................... 2

 

1-1. Check before use......................................................................... 2

 

1-2. Notes for use ............................................................................... 2

 

2. Installation and wiring........................................................................... 2

 

2-1. Installation site (environmental conditions)................................... 2

 

2-2. Mounting...................................................................................... 2

 

2-3. External dimensions and panel cutout ......................................... 2

 

2-4. Wiring .......................................................................................... 2

 

2-5. Terminal arrangement .................................................................. 3

 

3. Names and functions for front panel..................................................... 3

 

3-1. Names ......................................................................................... 3

 

3-2. Functions ..................................................................................... 3

 

4. Measuring range code table ................................................................. 3

 

5. Error messages.................................................................................... 3

 

6. Instruction for each screen ................................................................... 4

 

6-1. Screen sequences ....................................................................... 4

 

6-2. Power ON Screen Group ............................................................. 5

 

6-3. Mode 0 Screen Group.................................................................. 5

 

6-4. Mode 1 Screen Group.................................................................. 5

 

7. Optional features overview ................................................................... 7

 

7-1. Alarm output ................................................................................ 7

 

7-2. Analog output............................................................................... 7

 

7-3. Sensor power supply ................................................................... 7

 

8. Specification......................................................................................... 8

 

Safety Cautions 

 

WARNING

 

  The SD16A Series indicator is designed to indicate temperature, 

humidity and other physical data for general industrial equipment. Do 
not apply this instrument to other objects in a way that may cause 
grave effects on human safety.

 

  In using this product, be certain to house it, for example, in a control 

panel, so that the terminals cannot come into contact with personnel.

  Do not take this instrument out of its case or put your hand or any 

conductor inside the case. Such conduct may lead to an accident that 
endangers life or causes serious injury due to electric shock.

 

 

CAUTION 

  To avoid damage to the connected equipment, facilities or the product 

itself due to a fault of the product, safety countermeasure must be 
taken before usage, such as proper installation of the fuse and the 
overheating protection device.

 

  An alert symbol 

 is printed on the terminal nameplate attached to 

the case. It warns not to touch the electrical charging parts when the 
power is being supplied, so as to avoid the risk of electrical shock.

 

  Install a switch or breaker on the external source power circuit 

connecting to the source power terminal as a means to shut down the 
power.

 

The switch or breaker should be installed adjacent to the instrument 
in a position that allows the operator easy access.

 

 Regarding 

the 

fuse:

 

Since this instrument has no built-in fuse, make sure to install a fuse 
in the electric circuit connecting to the source power terminal.

 

Install the fuse in a position between the switch or breaker, and the 
instrument and attach it to the L side of the source power terminal.

 

Fuse Rating: 250V AC 1.0A/Time-lag (T) or Medium Time-lag (M)

 

  The load of voltage and current to be applied to the output terminal 

(analog output) and the alarm terminal must be within the rated 
range. If the range is exceeded, the instrument will overheat causing 
the risk of the instrument being damaged and its life reduced. 

 

As for the rating, please refer to "8. Specification."

 

The unit connected to the output terminal should conform to the 
requirements of IEC61010-1.

 

  Do not apply over-rated voltage or current to the input terminal. That 

will cause the risk of the instrument being damaged and its life 
reduced.

 

As for the rating, please refer to "8. Specification."

 

In case the input type is voltage (mV or V) or current (4 ~ 20mA), the 
unit connected to the output terminal should conform to the 
requirements of IEC61010-1.

 

  Take care to prevent metal or other foreign matter from obstructing 

the ventilating hole for heat radiation. It will cause damage to the 
instrument and may even result in fire.

 

  Do not block the ventilating hole. Also avoid dust accumulation. Any 

rise in temperature or insulation failure may result in a risk of the 
instrument being damaged and its life reduced. As for the clearance 
space for installing the instrument, refer to "2-3 External dimensions 
and panel cutout."

 

  Repeating withstanding tests on voltage, noise, surging may lead to 

the deterioration of the instrument, so please be careful.

 

  Strictly refrain from remodeling and using the instrument improperly.

 

 

Copyright © SHIMADEN CO., LTD. All rights reserved.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Содержание SD16A Series

Страница 1: ...injury due to electric shock CAUTION To avoid damage to the connected equipment facilities or the product itself due to a fault of the product safety countermeasure must be taken before usage such as...

Страница 2: ...2 Notes for use Avoid operating the front panel keys with hard or sharp objects Lightly touch the operating keys with your fingertips for operation When cleaning do not use a solvent such as a thinner...

Страница 3: ...st digit of the decimal point blinks until this registration by pressing the Entry key Shifts between a display screen and the setting screen In this case the light of the last digit of decimal point...

Страница 4: ...n is added Each screen is classified by the screen frame as follows Key operations on screens of Power ON Screen Group No key operation is required as screens alter automatically within Power ON Scree...

Страница 5: ...sic screen 0 0 KEEP RSET KEEP 0 3 PV bias The PV bias value is displayed or can be set The value is used for compensating input errors by the sensor etc When the value is set the compensated PV is dis...

Страница 6: ...he eset values are initialized However L The Alarm 2 action type is displayed or can be set As for action types refer to Ac Alarm o HA_L Higher limit absolute value with latching LA_L Lower limit abso...

Страница 7: ...f alarm optionally Action type The f rm output action types scree supported he lower limit absolute value alarm ollowing ala n 1 9 or 1 12 are T The higher limit absolute value alarm Scale over The la...

Страница 8: ...0V AC 1 5A resistive load Output update cycle 0 25 secs Isolation Isolated between alarm output and input between alarm output and analog output sensor power supply between alarm output and communicat...

Отзывы: