SD16A Instruction Manual
5
6-2. Power ON Screen Group
The following information is displayed automatically.
Model name
The model name (SD16A) is displayed.
Input type
The input type is displayed.
The type is either TC (thermocouple), Pt (R.T.D.),
mV, V, or mA.
Measuring range, lower-limit value
The lower-limit value of the input is displayed.
Measuring range, higher-limit value
The higher-limit value of input is displayed.
6-3. Mode 0 Screen Group
The following informational icons are used from this sub-section.
Setting/display is available
when the alarm option is
supported.
Setting/display is available when
the analog output option is
supported.
Setting/display is available
when the communication option
is supported.
Setting/display is available
when the voltage or current
input is specified.
Setting/display is not available
when the voltage or current input
is specified.
Setting range
Initial value
0-0 Basic screen
PV (measured value) is displayed.
Note
In case the Alarm 1 or 2 signal is output with the latching feature, use
key on this screen to release the Alarm 1 latching, or use
key on this screen to release the Alarm 2 latching.
0-1 Alarm 1 latching release
This screen is displayed when Alarm 1 is in the
latching state, and is used for releasing it from that
state.
This screen is displayed in case Alarm 1 code (1-1)
is selected from the one with latching, and when the
instrument is in the latching state. Set the parameter
RSET to stop the alarm output.
As for the latching feature, refer to "Latching feature"
of "7-1. Alarm output."
KEEP : Alarm output is ON with latching feature.
RSET : Releasing the alarm with latching feature.
Note
The Alarm 1 output signal with latching feature can also be set to OFF by
pressing
key on the Basic screen (0-0).
KEEP, RSET
KEEP
0-2 Alarm 2 latching release
This screen is displayed when Alarm 2 is in the
latching state, and is used for releasing it from that
state.
This screen is displayed in case Alarm 2 code (1-12)
is selected from the one with latching, and when the
instrument is in the latching state. Set the parameter
at RSET to stop the alarm output.
As for the latching feature, refer to "Latching feature"
of "7-1. Alarm output."
KEEP : Alarm output is ON with latching feature.
RSET : Releasing the alarm with latching feature.
Note
The Alarm 2 output signal with latching feature can also be set to OFF by
pressing
key on the Basic screen (0-0).
KEEP, RSET
KEEP
0-3 PV bias
The PV bias value is displayed or can be set.
The value is used for compensating input errors by
the sensor, etc. When the value is set, the
compensated PV is displayed.
-1999 ~ 2000 Unit
0 Unit
0-4 PV filter
The PV filter time is displayed or can be set.
The value is helpful for reducing the adverse effect
of noise from a PV input.
Note
The PV filtering is temporarily disabled when the instrument is recovering
from scale over.
0 ~ 100 seconds
100
0-5 Alarm1 setting value
Alarm 1 setting value is displayed or can be set.
One of the following Alarm 1 action types (1-9) is displayed on the screen.
A1HA :Higher-limit absolute value
A1LA :Lower-limit absolute value
A1H.A. :Higher-limit absolute value (with latching)
A1L.A. :Lower-limit absolute value (with latching)
Note
This screen is not displayed when non or So (scale over) is selected on
Alarm 1 code screen (1-9).
Measuring range lower-limit to higher-limit value
Higher-limit value
0-6 Alarm 2 setting value
Alarm 2 setting value is displayed or can be set.
One of the following Alarm 2 action types (1-12) is displayed on the screen.
A1HA
:Higher-limit absolute value
A1LA
:Lower-limit absolute value
A1H.A. :Higher-limit absolute value (with latching)
A1L.A. :Lower-limit absolute value (with latching)
Note
This screen is not displayed when non or So (scale over) is selected on Alarm
2 code screen (1-12).
Measuring range lower-limit to higher-limit value
Lower-limit value
6-4. Mode 1 Screen Group
1-0 Mode 1 initial screen
This is the heading screen of Mode 1 screens.
1-1 Key lock
Key lock status is displayed or can be set.
When the key lock is set to ON, parameter value
modification is not allowed.
OFF, ON
OFF
1-2 Display update cycle
The display update cycle of PV is displayed or can
be set.
0.25 ~ 5.00 secs. Set by 0.25 secs.
0.25
1-3 Measuring range
The input type is displayed or can be set. Refer to
"4. Measuring range code table" for input type
details.
01 ~ 12, 31 ~ 34, 71, 81 ~ 83, 95
05 (K, TC 0 ~ 1200°C)
1-4 Decimal places
The decimal place with/without status is
displayed or can be set.
dp_y : with decimal places
dp_n : without decimal places
Note
In case the measuring range that doesn’t support decimal places is specified,
this screen is not displayed.
Once this setting is modified from "with decimal places" to "without decimal
places", the values of input scaling, analog output scaling, alarm setting,
alarm hysterisis, and PV bias are rounded to the nearest integer. Then that
setting is modified to "with decimal places" again, the value after the decimal
places remains 0.
dp_y, dp_n
dp_y
mV
V
mA