SD16A Instruction Manual 

 

1. Introduction 

Note

 

The environmental conditions fall under installation category 
II of IEC 60664, and the pollution degree is "2".

 

1-1. Check before use

 

 

2-2. Mounting

 

Although the instrument passes thorough quality checks before shipment, 
when the instrument is delivered, please confirm the type code number, 
check the external conditions and the list of accessories to make sure that 
there is no apparent damage or discrepancy.

 

 

1  Cut a fitting hole by referring to the panel cutout dimensions in section 

2-3. The applicable thickness of the panel is 1.0 ~ 4.0mm. 

2  Insert the indicator into the hole from the front of the panel, as it has 

catching claws to fix it in position. 

Confirmation of the type code

 

Note

 

As the SD16A is a panel installation type indicator, use it by 
mounting on a panel.

 

Check the type code printed on the label on the packing case with the 
following table to confirm that the delivered goods meet your order.

 

 

Item

 

Code

 

Specifications

 

1. Series

 

SD16A-

 

48 × 96 DIN size    Digital Indicator

 

Universal-input

 

Š

 Thermocouple 

Š

 R.T.D. (Pt100, JPt100)

 

Š

 Voltage (Input impedance   

500 k

 min.)

 

Š

 0~10mV DC

 

Š

 0~5, 1~5, 0~10V DC

 

Refer to "4. Measuring 
range code table" for 
details.

 

In case voltage input, 
scaling/reverse scaling is 
available.

 

(Note 2)

 

2. Input (Note 1)

 

Current 4~20mA DC 
An external receiving resistor is 
provided.

 

Scaling/reverse scaling 
available (Note 2)

 

90- 

100~240V AC ± 10% (50/60Hz)

 

3. Power supply

 

08- 

24V AC (50/60Hz) /DC ±10%

 

None

 

4. Alarm output (option)

 

Separate setting/separate output 2-point (a-contact, 
"COM" used commonly)

 

Contact rating 240V AC    1.5A/resistive load

 

None

 

0~10mV DC Output resistance 10

 

4~20mA DC Load resistance 300

 

max.

 

0~10V DC Load current 1mA max.

 

Scaling/reverse 
scaling available
(Within 
measuring 
range)

 

5. Analog output

 

or sensor power supply 
(option) (Note 3)

 

Sensor power supply 24V±3V DC 25mA max.

 

None

 

RS-485

 

6. Communication function 

(option)

 

RS-232C

 

Without

 

7. Remarks

 

With

 

2-3. External dimensions and panel cutout

 

 

External dimensions

 

Unit: mm

 

Panel cutout

 

Note 1

 

The instrument supports full universal input; however please select one of two 
codes, as an external receiving resistor (250

) is supplied for current input. If 

no external receiving resistor is required, a code 8 specification product can 
be used for current input.

 

Note 2

 

Scaling range: -1999 ~ 9999 Unit 
Span: 10 ~ 10000 Unit

 

Note 3

 

When the 08 power supply code (24V AC/DC) is selected, the sensor power 
supply cannot be selected.

 

 

Accessory list check

 

 

  Unit label seal 

1 sheet

 

  Instruction Manual  1 copy

 

  Communication Interface Manual (in case the optional communication 

option is selected)  1 copy

 

 

Note

 

Contact our local agent or [email protected] via 
e-mail for any problems about the product, accessories or 
related items.

 

 

1-2. Notes for use

 

 

  Avoid operating the front panel keys with hard or sharp objects. Lightly 

touch the operating keys with your fingertips for operation.

 

  When cleaning, do not use a solvent such as a thinner. Wipe the 

instrument with a dry cloth lightly.

 

2. Installation and wiring 

 

2-1. Installation site (environmental conditions)

 

 

CAUTION 

Do not install the instrument in such environmental conditions as those 
listed below. Otherwise, damage may be caused to the instrument, even 
resulting in fire.

 

  Flammable or corrosive gas, oil soot or dust that deteriorates the 

insulation is generated or abundant.

 

  Ambient temperature is below 

10°C or above 50°C.

 

  Ambient humidity is higher than 90% RH, or below dew point.

 

  Strong vibrations or impacts are generated or transferred.

 

  High-voltage power lines exist in the neighborhood, or induction 

interference.

 

  Exposure to direct sunlight or dew drops.

 

  The elevation is above 2000m.

 

 

Unit: mm

 

2-4. Wiring

 

 

WARNING 

  When wiring the unit, be sure to cut the power supply OFF, or there 

will be a risk of electric shock.

 

  Make sure the protective conductor terminal (   ) is grounded.

 

Otherwise, a serious electric shock may result.

 

  After completing the wiring, do not touch the terminals and electrically 

charged parts while the power is ON.

 

 

  Make wiring according to the layout in "2-5. Terminal arrangement."

 

  Use ring tongue terminals of 7mm or narrower width to meet M3.5 

screws.

 

  In case of thermocouple input, use a compensation wire with the type 

of thermocouple selected. The external resistance should be100

 or 

less.

 

  In case of R.T.D. input, the resistance value per lead wire should be 5

 

or less, and all three wires should have the same resistance value.

 

  Avoid arranging the input signal line to pass through the same conduit 

or duct with high-voltage power lines.

 

  The shield wire (one-point grounding) is effective to eliminate 

electrostatic induction noises.

 

  An effective way to eliminate the magnetic induction noises is to twist 

the input wire in short and equal intervals.

 

  For the source power connection, use a wire or cable having a 

cross-section of 1mm

2

 or larger, and a performance capacity equivalent 

to 600V vinyl insulation wire.

 

  The grounding wire should have a cross-section of 2mm

2

 or larger, and 

the grounding work should ensure a ground resistance of 100

 or less.

 

 The 

symbol  expresses the functional earth terminal. Please connect 

it to the ground as much as possible to avoid the adverse impact from 
noise.

 

  Screw the terminal connection securely.

 

Tightening torque 1.1 · Nm (11kgf · cm)

 

 Noise 

filter

 

In case the instruments are affected by the power supply noise, install a 
noise filter to avoid operational errors.

 

Mount the noise filter on the grounded panel and connect the noise 
filter output and the power supply terminal of the indicator with the 
minimum possible distance.

 

 
 
 
 
 
 
 

Make wire with the mini-
mum possible distance

100~200V AC

100~200V AC

50/60 Hz

Noise filter

SD16A

Grounding

Recommended noise filter:

ZMB2203-13 from TDK

2

 

 

Содержание SD16A Series

Страница 1: ...injury due to electric shock CAUTION To avoid damage to the connected equipment facilities or the product itself due to a fault of the product safety countermeasure must be taken before usage such as...

Страница 2: ...2 Notes for use Avoid operating the front panel keys with hard or sharp objects Lightly touch the operating keys with your fingertips for operation When cleaning do not use a solvent such as a thinner...

Страница 3: ...st digit of the decimal point blinks until this registration by pressing the Entry key Shifts between a display screen and the setting screen In this case the light of the last digit of decimal point...

Страница 4: ...n is added Each screen is classified by the screen frame as follows Key operations on screens of Power ON Screen Group No key operation is required as screens alter automatically within Power ON Scree...

Страница 5: ...sic screen 0 0 KEEP RSET KEEP 0 3 PV bias The PV bias value is displayed or can be set The value is used for compensating input errors by the sensor etc When the value is set the compensated PV is dis...

Страница 6: ...he eset values are initialized However L The Alarm 2 action type is displayed or can be set As for action types refer to Ac Alarm o HA_L Higher limit absolute value with latching LA_L Lower limit abso...

Страница 7: ...f alarm optionally Action type The f rm output action types scree supported he lower limit absolute value alarm ollowing ala n 1 9 or 1 12 are T The higher limit absolute value alarm Scale over The la...

Страница 8: ...0V AC 1 5A resistive load Output update cycle 0 25 secs Isolation Isolated between alarm output and input between alarm output and analog output sensor power supply between alarm output and communicat...

Отзывы: