SD16A Instruction Manual 

8

8. Specification 

Display 

Digital display

Measured value (PV), 7-segment, Red 4-digit LED

Action indication

SET (green)  : lit when parameter value is displayed
COM (green)  : lit when communication mode is set
AL1/AL2 (red)  : lit when alarm signal is output

Display accuracy

± (0.3%FS + 1 digit) within measuring range
Excluding cold junction temperature compensation accuracy 

of thermocouple input.
± 5%FS for temperature below 400°C (752°F) of 

thermocouple B.
Accuracy of thermocouple T or U is ±0.5%FS at above -100°C 

and 0°C or below, and ±1%FS at -100°C or below.

Display accuracy 

maintaining range

23°C±5°C (18 ~ 28°C)

Display resolution

Differs depending on the measuring range (0.001, 0.01, 0.1, 1)

Measured value 

display range

-10 ~ 110% of measuring range (Accuracy is only guaranteed 

when the value is within the measuring range).
For R.T.D. input of  -199.9 ~ 600.0°C: -240.0 ~ 680.0°C

-199.9 ~ 500.0°C: -240.0 ~ 570.0°C

For thermocouple K of -199.9 ~ 800.0°C: -273.1 ~ 900.0°C

Display update cycle

0.25 ~ 5.00 secs (0.25 secs step)
When 0.50 secs or more is set, a difference may occur among 

the displayed value, the analog output, and the 

communication data.

Setting

Setting method

Using four key switches on the front panel
Setting protection feature by key lock ON/OFF is provided.

Setting range

Same as the measuring range.

Input 

Input type

Thermocouple, R.T.D., voltage (mV/V). Universal-input

Thermocouple

B, R, S, K, E, J, T, N {U, L (DIN43710)}, WRe5-26
For details, refer to the Measuring range code table.

Lead wire tolerable 

resistance

100Ω max.

Input impedance

500kΩ min.

Burnout

Standard feature (up-scale)

Cold junction 

compensation 

accuracy

±1°C (within accuracy maintain range (18 ~ 28°C))
±2°C (ambient temperature 5 ~ 18°C, 28 ~ 45°C)

R.T.D

JIS Pt100 3-wire type, JPt100 3-wire type

Amperage

Approx. 0.25mA

Lead wire tolerable 

resistance

5Ω max./wire (each wire should have the same resistance)

mV

0 ~ 10mV DC

 -l

oV

eg

at

V

0 ~ 5, 1 ~ 5, 0 ~ 10V DC

Input impedance 500kΩ

min.

Current

4 ~ 20mA DC

External receiving 

resistor

250Ω (supplied if specified)

Input scaling 

function

Available in case of voltage (mV/V) or current (mA) input.
Reverse scaling can be set.

Scaling range

-1999 ~ 9999 counts

Span

10 ~ 10000 counts

Decimal places

None, 0.0, 0.00, 0.000

Sampling cycle

0.25 secs

PV bias

-1999 ~ 2000

PV filter

0 ~ 100 secs (PV filter is set to OFF when 0 sec)

Isolation

Isolated between input and analog output (sensor power 

supply), or between input and communication. 
Not isolated between input and system.

Alarm output (option) 

Number of alarm 

points

2 points (AL1 and AL2), normally open, COM is commonly 

used.

Alarm type

One of the following six types can be assigned to each alarm.
None, higher-limit absolute value alarm (with latching), 

higher-limit absolute value alarm (without latching), lower-limit 

absolute value alarm (with latching), lower-limit absolute value 

alarm (without latching), Scale over

Setting range

Within measuring range or within scaling range

Alarm action

ON-OFF action

Hysteresis

1 ~ 999 Unit

Inhibit action

ON/OFF can be selected for each alarm output.

Output type

Contact 1a (COM is commonly used)

Rating

240V AC 1.5A (resistive load)

Output update cycle 

0.25 secs

Isolation

Isolated between alarm output and input, between alarm 

output and analog output (sensor power supply), between 

alarm output and communication, or between alarm output 

and system.
Not isolated between alarm output 1 and alarm output 2.

 

Analog output (option) 

Analog output type 

0 ~ 10mV (Output resistance 10Ω)
0 ~ 10V (Load current 1mA max.)
4 ~ 20mA (Load resistance 300Ω max.)

Output resolution 

Approx. 1/14000

Output accuracy 

±0.3%FS of display value

Scaling 

Within measuring range or within input scaling range (reverse 

scaling can be set).

Output update cycle 

0.25 secs

Isolation 

Isolated between analog output and input, between analog 

output and alarm output, between analog output and 

communication, or between analog output and system.

 

Sensor power supply (option) 

Output rating

24V ± 3V DC    25mA max. 

Depending upon instrument’s power ON-OFF status.

Isolation

Isolated between sensor power supply and input, between 

sensor power supply and alarm output, between sensor power 

supply and communication, or between sensor power supply 

and system.

Restrictions

Sensor power supply can't be selected when the analog 

output is selected. Sensor power supply can’t be selected 

when the power supply 24V is selected.

Communication (option) 

Communication type 

RS-232C, RS-485

Communication 

system

Half duplex asynchronous communication method

Communication 

speed

1200, 2400, 4800, 9600, 19200 bps

Data format

7E1, 7E2, 7N1, 7N2, 8E1, 8E2, 8N1, 8N2

Communication 

address

1 ~ 100

Number of 

connectable devices

31 devices max. (for RS-485)

Delay

1 ~ 100 msec

Communication 

protocol

Shimaden standard protocol, MODBUS ASCII, MODBUS 

RTU (start character and BCC operation method can be 

selected for Shimaden standard protocol).

Isolation

Isolated between communication and input, between 

communication and alarm output, between communication 

and analog output (sensor power supply), or between 

communication and system.

Miscellaneous 

Data storage

By nonvolatile memory (EEPROM).

Temperature

-10 ~ 50°C

Humidity

90%RH max. (no dew condensation)

Height

2000m above sea level or lower

Installation 

category

II

 s

noi

ti

dn

oc 

tn

ei

b

m

A

es

u r

of

Degree of 

pollution

2

Power supply voltage 

(frequency)

100 ~ 240V AC ± 10% (50/60Hz)
24V AC (50/60Hz) /DC ±10% (option)

Power consumption

11VA (100 ~ 240V AC)
8VA (24V AC)
5W (24V DC)

Safety

IEC61010-1, EN61010-1

 -il

pp

A

 el

ba

c

dr

ad

nat

s

EMC

EN61326:1997+A1:1998, A2:2001, A3:2003
EMC testing display accuracy ±3%FS

Dust proof /drip proof 

IP66 equivalent

Isolation resistance

Between all input/output terminals and power terminal: 
  500V DC 20MΩ min.
Between all input/output terminals and ground terminal: 
  500V DC 20MΩ min.

Dielectric strength

Between all input/output terminals and power terminal: 
  2300V AC for one minute.
Between power terminal and ground terminal: 
  1500V AC for one minute.

Case material

Black PPO resin molding (equivalent to UL94V-1)

External dimensions

H48 x W96 x D111 mm (inside of panel: 100mm)

Mounting

Push-in panel (one-touch mount)

Panel thickness

1.0 ~ 4.0 mm

Panel cutout

H45 x W92 mm

Weight

Approx. 250g

 
 

The contents of this manual are subject to change without notice. 

 

Any questions should be directed to your local agent, or send an e-mail to [email protected].

Printed in Japan

Содержание SD16A Series

Страница 1: ...injury due to electric shock CAUTION To avoid damage to the connected equipment facilities or the product itself due to a fault of the product safety countermeasure must be taken before usage such as...

Страница 2: ...2 Notes for use Avoid operating the front panel keys with hard or sharp objects Lightly touch the operating keys with your fingertips for operation When cleaning do not use a solvent such as a thinner...

Страница 3: ...st digit of the decimal point blinks until this registration by pressing the Entry key Shifts between a display screen and the setting screen In this case the light of the last digit of decimal point...

Страница 4: ...n is added Each screen is classified by the screen frame as follows Key operations on screens of Power ON Screen Group No key operation is required as screens alter automatically within Power ON Scree...

Страница 5: ...sic screen 0 0 KEEP RSET KEEP 0 3 PV bias The PV bias value is displayed or can be set The value is used for compensating input errors by the sensor etc When the value is set the compensated PV is dis...

Страница 6: ...he eset values are initialized However L The Alarm 2 action type is displayed or can be set As for action types refer to Ac Alarm o HA_L Higher limit absolute value with latching LA_L Lower limit abso...

Страница 7: ...f alarm optionally Action type The f rm output action types scree supported he lower limit absolute value alarm ollowing ala n 1 9 or 1 12 are T The higher limit absolute value alarm Scale over The la...

Страница 8: ...0V AC 1 5A resistive load Output update cycle 0 25 secs Isolation Isolated between alarm output and input between alarm output and analog output sensor power supply between alarm output and communicat...

Отзывы: