Detailed Function Description
56
Notice: When the traverse amplitude set is too large, result in
output frequency during traverse running will be higher than Upper
limit, traverse running will be automatically invalid.
Output frequency
Traverse ampltude
Setting frequency
Skip amplitude
0
Run command
run
Fall time of traverse Rise time of traverse
stop
time
Chart 5-9 Traverse frequency run diagram
5.1.11 Serial Communication Settings
P0-055
Local address
Setting range
:
1
~
32
Factory value
:
1
During serial communication, the identification address of inverter.
1
~
31: address of slave inverter.
32: address of master inverter (be used by many inverters at the
same time).
Содержание DK00 Series
Страница 1: ...DK00 Series Inverter User Manual V1 3...
Страница 3: ...2 3 Installation dimensions of inverter 12 2 4 Installation dimension of keyboard 14 3 wiring 15...
Страница 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Страница 7: ...5 1 11 Serial Communication Settings 56...
Страница 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Страница 11: ...9 3 Examples of MODBUS Information 100...
Страница 13: ...Chart Index 109...
Страница 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Страница 85: ...72 Fault and trouble shooting...
Страница 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Страница 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...