Detailed Function Description
37
P0-015
Automatic slip
Setting range
:
0.0
~
Factory value
:
100.0
%
compensation gain
250.0
%
The function is used to improve the motor speed by reason of load
changes. When Load is stable, if the motor fluctuation of rotate
speed is large, please reduce the function code.
This function code for 0.0 mean that the automatic slip
compensation is prohibited.
5.1.3 Input terminals
P0-016
X1 terminal function
Setting range
:
0
~
14
Factory value
:
1
P0-017
X2 terminal function
Setting range
:
0
~
14
Factory value
:
2
P0-018
X3 terminal function
Setting range
:
0
~
14
Factory value
:
4
P0-019
X4 terminal function
Setting range
:
0
~
14
Factory value
:
9
0: invalid. Idle input terminals.
1: Forward run. Forward run command input.
2: Reverse run. Reverse run command input.
Содержание DK00 Series
Страница 1: ...DK00 Series Inverter User Manual V1 3...
Страница 3: ...2 3 Installation dimensions of inverter 12 2 4 Installation dimension of keyboard 14 3 wiring 15...
Страница 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Страница 7: ...5 1 11 Serial Communication Settings 56...
Страница 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Страница 11: ...9 3 Examples of MODBUS Information 100...
Страница 13: ...Chart Index 109...
Страница 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Страница 85: ...72 Fault and trouble shooting...
Страница 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Страница 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...