Detailed Function Description
47
P0-036
Over-current protection value
Setting range
:
Factory value
:
150.0%
when lose speed
110.0%~200.0%
This 100.0% of function code corresponding to rated current of
inverter.
Surge current phenomenon of inverter will occur in the accelerating
running process , due to acceleration time and motor inertia does
not match or load inertia alters suddenly . By checking the inverter
output current, and with this setting value of function code to
compare, when the actual current exceeds the value, the Acc speed
will be suspended until the current is reduced to less than the 5.0%
of setting value.
Содержание DK00 Series
Страница 1: ...DK00 Series Inverter User Manual V1 3...
Страница 3: ...2 3 Installation dimensions of inverter 12 2 4 Installation dimension of keyboard 14 3 wiring 15...
Страница 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Страница 7: ...5 1 11 Serial Communication Settings 56...
Страница 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Страница 11: ...9 3 Examples of MODBUS Information 100...
Страница 13: ...Chart Index 109...
Страница 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Страница 85: ...72 Fault and trouble shooting...
Страница 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Страница 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...