Detailed Function Description
45
P0-030
Keyboard STOP key
function setting
Setting range
:
0
~
1
Factory value
:
0
0: It is invalid in the analog terminal / serial communication control
mode.
1: It is effective in the analog terminal / serial communication
control mode (equivalent to the external fault input).
5.1.6 Start and Stop Control
P0-031
Stop mode
Setting range
:
0
~
1
Factory value
:
0
0: Deceleration to stop. When the stop command takes effect, the
inverter decreases the output frequency, according to the selected
Acc/Dec time till stop.
1: Coast to stop.When the stop command takes effect, the inverter
stops the output immediately. The motor coasts to stop by its
mechanical inertia.
Содержание DK00 Series
Страница 1: ...DK00 Series Inverter User Manual V1 3...
Страница 3: ...2 3 Installation dimensions of inverter 12 2 4 Installation dimension of keyboard 14 3 wiring 15...
Страница 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Страница 7: ...5 1 11 Serial Communication Settings 56...
Страница 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Страница 11: ...9 3 Examples of MODBUS Information 100...
Страница 13: ...Chart Index 109...
Страница 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Страница 85: ...72 Fault and trouble shooting...
Страница 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Страница 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...