Page 7 di 32
PTU50-51-56 -
installation
5-
INSTALLATION
5.1 MOUNTING PRECAUTIONS
5.1.1 Mounting position
- With cambered roof, Do not install the sensor in the tank center (b). Leave a 300mm (d) minimum distance
between the sensor and the tank smooth wall.
- Use a protective cover to protect the sensor from weather and direct sunlight (c).
- Do not install the sensor near the load zone (a).
- Make sure that in the sensor emission beam (lobe “α”) there are no obstacles (f,s) that can be
intercepted as level.
- Make sure that there is not foam presence on the product surface to be measured.
5.1.2 Blind distance
During installation is important to remember that in the sensor vicinity there is a blind zone (or BLIND DISTANCE)
of 0.05m (for 1.5m max PTU50 range), 0.3m (for 6m max PTU51 range) or 0.5m (for 12m max PTU56 range) where
the sensor can not measure.
Lobo “
α
“
PTU50 1,5mt
5°
PTU51 6mt
5°
PTU56 12mt
5°
PTU50 0,05mt (1,5mt)
PTU51 0,3mt (6mt)
PTU56 0,5mt (12mt)
Blind Distance