Page 14 of 32
Quick Setup
Set Distance 4mA
Set Distance 20mA
Medium
Filter Coefficient
Blind Distance
Display
Set Distance 4mA
0000 mm
Set Distance 20mA
0000 mm
Filter Coefficient
000
Blind Distance
0000 mm
Distace mm
Level mm
Level %
Output mA
Temperature °C
Parameter Default Values
1500mm (PTU50 1.5mt max)
6000mm (PTU51 6mt max)
12000mm (PTU56 12mt max)
Liquids
20
Distance mm
100mm (PTU50 1.5mt max)
400mm (PTU51 6mt max)
600mm (PTU56 12mt max)
050mm (PTU50 1.5mt max)
300mm (PTU51 6mt max)
500mm (PTU56 12mt max)
Medium
>Liquids
Solids
Liquids Pipe
PTU50-51-56 -
quick setup
8.2 - QUICK SETUP MODE
From “RUN” mode press ENTER to access the Quick Setup menu.
Select the parameters by moving the cursor with SCROLL, and confi rm with
ENTER; press LEFT ARROW to exit.
DISTANCE 4mA
DISTANCE 20mA
MEDIUM
FILTER COEFFICENT
BLIND DISTANCE
DISPLAY
Ź
4321
D
mm
8-QUICK SETUP
8.1 - Quick Setup menu structure