Page 28 of 32
9.6.5.1 - DISPLAY VALUES
Position the cursor on DISPLAY VALUES, press ENTER to access.
Displays the max. and min. distance measured from power on.
LEFT ARROW to exit.
NB - The peak values stored are erased every time the
PTU50-51-56 turns-off l
PTU50-51-56 -
advanced confi guration
9.6.5.2 - RESET VALUES
Position the cursor on RESET VALUES, press ENTER to access.
LEFT ARROW to return to the previous menu
9.6.6 - OUTPUT SIMULATION
WARNING - entering in the SIMULATION function, the current output is not
in function of the level measurement. To restore the current as a measured
level function, press the LEFT ARROW button 3 times (RUN mode)
Position the cursor on OUTPUT SIMULATION, press ENTER to access.
It’s possible to force the analog output to a desired value, from 3,5 to
21mA.
Use UP ARROW and SCROLL to modify the value.
LEFT ARROW to return to the previous menu.
DISPLAY VALUES
RESET VALUES
Ź
MAX 0000mm
MIN 0000mm
PEAK VALUES
DISPLAY VALUES
RESET VALUES
Ź
ALARM CONFIGURATION
MEASURE STATUS
FROZEN GAIN
MAX GAIN TH.
PEAK VALUES
OUTPUT SIMUL.
Ź
04.0mA
OUTPUT SIMUL.