OVERPRESSURE – LEAK DETECTOR DL ..
3.3 Air or liquid leak
If a leak occurs below or above the liquid level or ground water, leak detection medium escapes
from the interstitial space. Pressure falls until the pressure generator is switched on to restore
the operating pressure. If the volume flow escaping out of the leak is greater than the refill
intake from the pressure generator, then the pressure in the system falls although the pressure
generator is activated.
Enlargement of the leak causes a further loss in pressure until the alarm pressure is reached.
The visual and audible alarm is triggered.
3.4 Air drying / dry filter (DL . ONLY)
The air fed to the interstitial space passes through a dry filter in the suction line. The dry filter
dries the air to approx. 10% humidity to prevent corrosion and accumulation of condensation
1
the interstitial space.
The dry filter is rated for twelve months as long as the system is used for its intended use and
there are no additional fluctuations in temperature.
A dry filter is orange when new and turns colourless
(or green)
when spent. Spent dry filters
must be
replaced or regenerated without delay.
3.5 Overpressure
valve
The overpressure valve integrated in the pressure line protects the interstitial space from
intolerably high overpressure (exceeding the test pressure).
Intolerably high overpressure can be caused among others by:
•
increase in ambient temperature (e.g. direct sunshine)
•
increase in temperature from hot filling (possibly consult manufacturer)
3.6 Description of the display and control elements
3.6.1 Status of the display elements (LEDs) for type DL ..
LEDs
Operating status Alarm status
Alarm, audible alarm
switched off
Unit out of order
OPERATION:
green
ON ON
ON
ON
ALARM:
red
OFF O
N
FLASHES
ON
1
Accumulation of condensation in the interstitial space can cause an intolerable pressure increase.
26/01/2006
4
7 von 49
Содержание DL 100
Страница 19: ...I I II II III III IV IV 21 21 21 21 20 20 20 20 27 11 2002 P 060 000 Druckleitung Messleitung 19 von 49 ...
Страница 20: ...Ex Ex Ex 17 102 72 73 43 13 27 11 2002 M1 060 000 76 30 21 20 70 20 von 49 ...
Страница 21: ...Ex Ex Ex 73 73 73 230 V 50 Hz 21 02 43 20 13 72 27 11 2002 M2 060 000 71 69 01 09 21 von 49 ...
Страница 22: ...27 11 2002 M3 065 000 45 71 29 69 01 09 103 104 14 Ex Ex Ex 73 73 73 230 V 50 Hz 21 02 43 20 13 22 von 49 ...
Страница 24: ...27 11 2002 SL 853 600 2 6 4 5 3 11 12 1 AC DC 105 106 102 71 01 69 24 1 59 09 76 17 60 Rp 24 von 49 ...
Страница 26: ...22 84 85 85 22 52 98 98 0 Kl 1 0 17 12 2002 P 115 392 21 21 20 20 90 90 26 von 49 ...
Страница 34: ...28 06 2005 Drilling Dimension 200 300 260 220 T 140 8 34 von 49 ...