OVERPRESSURE – LEAK DETECTOR DL ..
1 Subject
Overpressure leak detector for double-walled tanks with pressure provided either by a pump or
by a compressed gas supply.
DL ..
Overpressure leak detector with integrated pump. Dots stand for alarm pressure.
DLG .. Overpressure leak detector with compressed gas supply. Dots stand for alarm pressure
2 Field of application
2.1 Requirements for interstitial space
•
Evidence of the pressure resistance of the interstitial space (see Annex B, column "p
TEST
"
minimum test pressure of the interstitial space)
•
Evidence of the suitability of the interstitial space (for Germany: Building Inspectorate
Suitability Serification)
•
Tightness of the interstitial space (see chap. 6.4.4)
•
The number of interstitial spaces for monitoring in
underground tanks
depends on the total
interstitial space volume. According to prEN 13160, 8 m
3
must not be exceeded. It is
recommended not to exceed 4 m³ with regard to the feasibility of monitoring the tightness of
the interstitial space.
2.2 Tanks/interstitial space (see chapter 2.4)
•
Under- and above ground double-walled steel or plastic tanks, without leak detection liquid
in the interstitial space, manufactured in the factory or on site, whose interstitial space is
suitable for the connection of a DL .. as per Annex B.
•
Under- and above ground single-walled steel or plastic tanks with pressure-resistant leak
detection lining or leak detection jacketing, whose interstitial space is suitable for the
connection of a DL .. as per Annex B.
•
Double-walled sumps or containments with interstitial space suitable for the connection of a
DL .. as per Annex B.
2.3 Stored
products
Liquids hazardous to water with regard to the following points:
•
The leak detection medium must not react with the stored products.
•
Vapour/air mixtures resulting from the
-
stored liquid
-
stored liquid in combination with air / humidity or condensation
-
stored liquid in combination with parts (materials) in contact with the liquid
must be classified in gas group IIA and II B and in temperature code T1 to T3.
26/01/2006
2
5 von 49
Содержание DL 100
Страница 19: ...I I II II III III IV IV 21 21 21 21 20 20 20 20 27 11 2002 P 060 000 Druckleitung Messleitung 19 von 49 ...
Страница 20: ...Ex Ex Ex 17 102 72 73 43 13 27 11 2002 M1 060 000 76 30 21 20 70 20 von 49 ...
Страница 21: ...Ex Ex Ex 73 73 73 230 V 50 Hz 21 02 43 20 13 72 27 11 2002 M2 060 000 71 69 01 09 21 von 49 ...
Страница 22: ...27 11 2002 M3 065 000 45 71 29 69 01 09 103 104 14 Ex Ex Ex 73 73 73 230 V 50 Hz 21 02 43 20 13 22 von 49 ...
Страница 24: ...27 11 2002 SL 853 600 2 6 4 5 3 11 12 1 AC DC 105 106 102 71 01 69 24 1 59 09 76 17 60 Rp 24 von 49 ...
Страница 26: ...22 84 85 85 22 52 98 98 0 Kl 1 0 17 12 2002 P 115 392 21 21 20 20 90 90 26 von 49 ...
Страница 34: ...28 06 2005 Drilling Dimension 200 300 260 220 T 140 8 34 von 49 ...