Manual – DFD11B DeviceNet Fieldbus Interface
71
8
Diagnostic procedures
Error Diagnostics
Step 3: Troubleshooting
When DFD11B is in status 'Connected' or 'Module error' the data exchange between
master (scanner) and slave (DFD11B) is active. If it is still possible to run the drive via
DeviceNet, the following questions should help to find the reason.
A Are the right values displayed for the process data words in MOVITOOLS
®
Motion-
Studio? Parameter group 09 (MOVIDRIVE
®
B) or process data (Gateway).
→
if yes, proceed with F.
B Is bit 0 in DeviceNet control register of the PLC set to '1' to activate the process data
exchange?
C Are the process data words copied to the right offset in the Local I/O tag of the De-
viceNet scanner? Check in controller tags and scanner mapping.
D Is the PLC in RUN mode or does active forcing overwrite the transfer of the normal
process data words?
E If the PLC is not sending data to the DFD11B, please refer to the documentation of
the PLC manufacturer for support.
F Is the DFD11B mounted into MOVITRAC
®
B or gateway housing?
→
if yes, proceed with H.
G In MOVIDRIVE
®
B, is
P100 control source
and
P101 setpoint source
= FIELDBUS?
→
proceed with L
H Are all drives connected to the SBus of the gateway accessible from MOVITOOLS
®
MotionStudio via serial interface X24 of the gateway?
Check SBus addresses and SBus baud rate.
I
Is LED H1 on the gateway off?
J Has the Auto Setup function (DIP switch AS) been executed with all drives connected
to the SBus and supplied with power?
K In MOVITRAC
®
B connected to the gateway, is
P100 control source
and
P101 set-
point source
= SBus 1?
L Are the process data words in the drive configured correctly (P870 ... P875)?
M Is process output data enabled (P876) = ON?
N Is the wiring of the binary inputs disabling the operation?
Check parameter group P03_ and P04_.
O Is an error active? What is the state of the unit?
P Is an IPOS
plus®
program active, which e. g. affects the inverter status?