Manual – DFD11B DeviceNet Fieldbus Interface
41
5
Programming samples in RSLogix 5000
Project Planning and Startup
Only few changes are required for parameter write access:
• Define the controller tags (
→
following figure).
• Create a rung for the WriteParameter execution (
→
following figure).
For contact, select the tag 'WriteParameterStart'
For the Message Control, select the tag 'WriteParameter'
• Click on
in the MSG instruction to open the Message Configuration Window
(
→
following figure).
Fill in the data in the following order:
– Source Element = WriteParameterRequest.Index
– Source Length = 12
– Destination = WriteParameterResponse.Index
– Class = 7
hex
– Instance = 2
– Attribute = 4
hex
– Service Code = 10
hex
11771AXX
11772AXX
11773AXX
0
0
I