![SEW DFD11B Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/sew/dfd11b/dfd11b_manual_1250019067.webp)
Manual – DFD11B DeviceNet Fieldbus Interface
67
6
Return codes for parameter setting via explicit messages
DeviceNet Characteristics
General error
codes
DeviceNet-specific error codes
General error
code (hex)
Error name
Description
00 - 01
Reserved for DeviceNet
02
Resource unavailable
The source required for performing the service is unavailable
03 - 07
Reserved for DeviceNet
08
Service not supported
The service is not supported for the selected class/instance
09
Invalid attribute value
Invalid attribute data have been sent
0A
Reserved for DeviceNet
0B
Already in requested
mode/state
The selected object is already in the requested mode/state
0C
Object state conflict
The selected object cannot perform the service in its current
status
0D
Reserved for DeviceNet
0E
Attribute not settable
It is not possible to access the selected object for writing.
0F
Pivilege violation
Violation of access entitlement
10
Device state conflict
The current status of the device makes it impossible to perform
the required service
11
Reply data too large
The length of the transmitted data is longer than the size of the
receive buffer
12
Reserved for DeviceNet
13
Not enough data
The length of the transferred data is too short for the service to
be performed
14
Attribute not supported
The selected attribute is not supported
15
Too much data
The length of the transferred data is too long for the service to
be performed
16
Object does not exist
The selected object is not implemented in the device
17
Reserved for DeviceNet
18
No stored attribute data
The requested data have not been stored previously
19
Store operation failure
The data could not be stored because an error occurred while
saving them
1A - 1E
Reserved for DeviceNet
1F
Vendor specific error
Vendor specific error (
→
Manual"SEW Fieldbus Device Pro-
file")
20
Invalid parameter
Invalid parameter
This error message is used when a parameter does not satisfy
the requirements of the specification and/or the requirements of
the application.
21 - CF
Future extensions
Reserved by DeviceNet for additional definitions
D0 - DF
Reserved for Object
Class and service
errors
Use this area if an occurring error cannot be entered in one of
the error groups listed above.
0
0