MOVITRAC
®
0500
Frequency Inverters
Operating Instructions
Edition 01/97
09
22
3
9
1
6
/
0
19
7
Страница 1: ...MOVITRAC 0500 Frequency Inverters Operating Instructions Edition 01 97 0922 3916 0197...
Страница 2: ...underneath terminal strip X1 8 Terminal strip X1 electronic control connections 9 Terminal strip X5 power section Terminal strips X1 and X5 are included with the unit they are placed on the unit and s...
Страница 3: ...ed potentiometer 15 4 3 Setting the signal mode for FSINA and SOUTA 16 4 4 Complete parameter list 17 4 4 1 Menu branch VAL display parameters 17 4 4 2 Menu branch PARA adjustable parameters 18 5 Oper...
Страница 4: ...rves the right to make alterations to the technical data and design which serve the cause of technical progress Storage instructions Permissible storage temperature 25 C 70 C Permissible humidity No r...
Страница 5: ...mpliance with EMC regulations Sec 3 2 with EMC Directive 89 336 EEC Type designation Example MOVITRAC 0504 231 1 00 Version 00 standard Quadrants 1 1 quadrant Type of supply 1 single phase Rated suppl...
Страница 6: ...ng displays H1 and H2 or any of the other status indicators go out this does not mean that the inverter is disconnected from the supply and is de energized Protective measures and equipment must be ch...
Страница 7: ...inverter is inhibited Only an inductive resistive load motor may be connected at the inverter output no capacitive load For jogging use the commands clockwise STR counterclockwise STL The mains conta...
Страница 8: ...1 input filter MOVITRAC 0508 231 1 00 NF008 231 input filter Mount the NF input filter close to the corresponding MOVITRAC 0500 but outside the minimum ventilation space required Keep the connecting l...
Страница 9: ...t limit Imax 50 mA 9 brake chopper active 10 disconnection on faults 10 SOUTA Analog binary output Imax 2 mA analog Imax 15 mA binary Important not short circuit proof do not apply external source vol...
Страница 10: ...e control an external 24 V supply is necessary The binary output drives an external brake relay K1 24 V 1 2 W max 50 mA This relay controls the brake via a brake contactor K2 The brake must be actuate...
Страница 11: ...the supply 5 Start the drive in the direction of rotation you require X1 3 STR or X1 4 STL 1 The drive will start if setpoint input 0 1 V 0 5 Hz or one of the fixed setpoints is selected Important if...
Страница 12: ...urn 4 Labelling field for bar graph display 5 Arrow key up 6 Key Start Enter 7 Optional ParaCard PAC 01 8 Connecting cable FBG 01 inverter 9 Dimension for bar graph display 10 5 digit actual value and...
Страница 13: ...menu branches or parameters Cancels changes The menu is structured as follows VAL display values PARA adjustable parameters In parameter 01 MODE operating mode three operating modes can be selected T...
Страница 14: ...changed when the inverter is inhibited When the unit is enabled and started the parameters can only be read Adjustable parameters Sec 4 4 2 Manual operation can only be selected if the unit is inhibi...
Страница 15: ...The inverter will decelerate to 0Hz using ramp 33 RDEC1 reverse and accelerate to the frequency input with ramp 32 RACC1 The inverter will decelerate to standstill with ramp 33 RDEC1 Fig 7 Manual ope...
Страница 16: ...10 kW or external voltage source 0V STOP output inhibited 0 1 V FMIN 10 V FMAX 2 10 V external power supply 0 20 mA 4 20 mA zero live signal Analog binary output SOUTA X1 10 Input signal Jumper J3 J4...
Страница 17: ...X 16 PW Active power 0 18000 W X X X 17 VZK DC link voltage 0 350 900 V X X X 18 TIME Operating time from reset 0 0 960 0 h X X X 19 TOP Operating hours 0 60000 h X 66 SIN Not for use X 68 FIN X 83 S...
Страница 18: ...cy 0 00 999 00 X X 29 FMAX2 Maximum frequency 4 00 50 00 999 00 Ramp generators X X 31 KSEL Characteristic set selector 0 1 2 3 0 always data set 1 1 data set 2 if 12 F 26 FF6 2 data set 2 if S2IND 1...
Страница 19: ...MC0508 0 90 3 20 A Control functions X X 61 SOUTA Analog output X1 10 0 1 7 Sec 3 4 4 3 X X 62 S1OUT Digital output 1 X1 8 0 1 10 Sec 3 4 X X 63 S2OUT Digital output 2 X1 9 1 7 10 Sec 3 4 X X 64 SINA...
Страница 20: ...RDEC1 or 35 RDEC2 reverses and accelerates with ramp 32 RACC1 or 34 RACC2 STR and STL 1 Important not fail safe Deceleration with deceleration ramp Drive decelerates with ramp 33 RDEC1 or 35 RDEC2 STR...
Страница 21: ...r overtemperature Motor overloaded check drive or check PTC thermistor connection or jumper X5 PTC IIIIIIII IIIIIIII 8 times Inverter overtemperature Inverter overloaded check installation and ambient...
Страница 22: ...patible ERR96 Connection to PAC 01 interrupted ERR97 PAC 01 invalid CS test Inverter faults E CPU Fault in processor pcb AUTOSTART in 72 START causes reset 1 E OFF Undervoltage no entry in fault memor...
Страница 23: ...eration BRC 03 with integrated braking resistor Interference emission with EMC compliant installation mains input filter screened motor cable to class B limit to EN 55011 EN 55014 complies with EN 500...
Страница 24: ...Imax 50 mA Important not short circuit proof not external voltage proof Reference potential ground X1 7 or X1 11 Programmable collective fault output voltage CW CCW motor standstill setpoint reached...
Страница 25: ...ns 40 x170 mm hole size 4 8 mm For use with MOVITRAC type 0504 231 1 0508 231 1 cdf cyclic duration factor 6 3 NF 231 input filter Input filter type NF 005 231 NF 008 231 Part number 825 881 3 825 882...