Assembly / Installation Instructions
Installation of MOVI-PLC® basic DHP11B.. controller
22
Manual – MOVI-PLC
®
basic DHP11B.. controller
PLC status LED
The
PLC status
LED indicates the firmware status of the MOVI-PLC
®
basic
DHP11B..
controller.
IEC program
status LED
The
IEC program status
LED indicates the status of the IEC 61131 control program.
Run Profibus LED
The
Run Profibus
LED indicates the proper functioning of the PROFIBUS electronics
(hardware).
Fault Profibus
LED
The
Fault
Profibus LED indicates that communication via the PROFIBUS interface is
working properly.
PLC
status
Diagnostics
Remedy
Flashing
green
(1 Hz)
•
Firmware of the MOVI-PLC
®
basic
DHP11B.. controller is running correctly.
–
IEC
program
status
Diagnostics
Remedy
Green
•
IEC program is running.
–
Off
•
No program is loaded.
Load the program into the controller.
Flashing
orange
(1 Hz)
•
Program has stopped.
–
RUN
Profibus
Diagnostics
Remedy
Green
•
PROFIBUS hardware OK.
–
Flashing
green
(1 Hz)
•
The PROFIBUS station address set on the
DIP switches is more than 125. If the
PROFIBUS station address is set to a value
higher than 125, the MOVI-PLC
®
basic
DHP11B.. controller will use PROFIBUS
station address 4.
1. Check and correct the PROFIBUS
station address on the DIP switches.
2. Switch on all drive inverters again. The
modified PROFIBUS address will only
take effect after a restart.
BUS
FAULT
Diagnostics
Remedy
Off
•
The MOVI-PLC
®
basic
DHP11B.. controller
exchanges data with the PROFIBUS-DP
master (data exchange status).
–
Red
•
Connection to the DP master has failed
•
The MOVI-PLC
®
basic
DHP11B.. controller
does not recognize the PROFIBUS baud
rate.
•
Bus interruption has occurred.
•
PROFIBUS-DP master not in operation.
•
Check the PROFIBUS connection on
the unit.
•
Check project planning of the
PROFIBUS-DP master.
•
Check all the cables in the PROFIBUS
network.
Flashing
red
(1 Hz)
•
The MOVI-PLC
®
basic DHP11B.. controller
recognizes the baud rate. However, the DP
master does not address the MOVI-PLC
®
basic
DHP11B.. controller.
•
The MOVI-PLC
®
basic
DHP11B.. controller
was either not configured in the DP master
or it was configured incorrectly.
•
Check and correct the PROFIBUS
station address set in the MOVI-PLC
®
basic
DHP11B.. controller and in the
configuration software of the DP
master.
•
Check and correct the configuration of
the DP master.
•
Use the GSD file
SEW_6007.GSD
with
the designation
MOVI-PLC
for configu-
ration.