Sensors wiring and control board setting:
ID
SENSORE
SCHEMA
17=0
30=1
Safety monitoring sensor in closing (ref. Fig.39 A)
ref. Fig.22
17=0
30=1
Safety monitoring sensor in opening (ref. 39 B)
ref. Fig.23
Detection sensor (radar) entry (ref. Fig.39 D)
ref. Fig.24
Detection sensor (radar) exit (ref. Fig.39 C)
ref. Fig.25
If monitored sensors configuration has not been memorized, on display appears E6 error. Exit
fr
om this status through procedure LS, see paragraph “parameters adjustment –
display”.
During this procedure control board checks which sensors are connected and checks if they
are correctly working.
ATTENTION during LS procedure stay away from sensors and be sure they are not
detecting obstacles. In case they are not correctly wired or working, LS blinks. Abort procedure
pushing ESC. Checks sensors and launch LS again.
At the end of LS procedure display shows one of the following configurations:
ID
CONFIGURATION
DESCRIPTION
S0
No monitored sensor
detected
There are no monitored sensors wired or the sensors
connected will be managed as a normal sensors without
monitoring.
S1
monitored sensor only in
opening.
There is only monitored sensor in opening. In closing there
is no sensor connected or the sensor connected will be
managed as a normal sensor without monitoring.
S2
monitored sensor only in
closing.
There is only monitored sensor in closing. In opening , there
is no sensor connected or the sensor connected will be
managed as a normal sensors without monitoring.
S3
monitored sensor in
opening and closing.
There are monitored sensors wired both in closing and
opening.
The indication remains on the display until it is pressed one of the following push buttons:
-
ENT: to confirm the configuration indicated, making sure that it correspond to the
real configuration of the connected sensors;
-
ESC: to abort the detected configuration and go back to the error status E6.
ATTENTION: never confirm the detected configuration if does not correspond to the
real configuration of the connected sensors. This might create danger situations or
malfunction of the automatism.
LS procedure can be repeated in any occasion through the parameter LS (look at
paragraph “parameters adjustment –
display”
).
Содержание PROSWING R
Страница 1: ...P R O S W I N G R ENGLISH OPERATOR FOR SWINGING DOORS MANUAL INSTRUCTIONS...
Страница 2: ......
Страница 26: ...26 SESAMO PROSWING...
Страница 27: ...27 SESAMO PROSWING Fig 1 Fig 2 Fig 3...
Страница 28: ...28 SESAMO PROSWING Fig 4...
Страница 29: ...29 SESAMO PROSWING Fig 5...
Страница 30: ...30 SESAMO PROSWING Fig 6...
Страница 31: ...31 SESAMO PROSWING Fig 7...
Страница 32: ...32 SESAMO PROSWING Fig 8...
Страница 33: ...33 SESAMO PROSWING Fig 9 Fig 10...
Страница 34: ...34 SESAMO PROSWING Fig 11 Fig 12...
Страница 35: ...35 SESAMO PROSWING Fig 13 Fig 14 Fig 15 Fig 16...
Страница 36: ...36 SESAMO PROSWING Fig 17 Fig 18 m Kg...
Страница 37: ...37 SESAMO PROSWING Fig 19...
Страница 38: ...38 SESAMO PROSWING Fig 20 Fig 21...
Страница 39: ...39 SESAMO PROSWING Fig 22...
Страница 40: ...40 SESAMO PROSWING Fig 23...
Страница 41: ...41 SESAMO PROSWING Fig 24 Fig 25...
Страница 42: ...42 SESAMO PROSWING Fig 26 Fig 27...
Страница 43: ...43 SESAMO PROSWING Fig 28 Fig 29...
Страница 44: ...44 SESAMO PROSWING Fig 30 Fig 30...
Страница 45: ...45 SESAMO PROSWING Fig 31...
Страница 46: ...46 SESAMO PROSWING...
Страница 47: ......