TROUBLESHOOTING

PROBLEM

CAUSE

SOLUTION

The motor reducer 
does not work

No voltage to 
the motors

—

 Check the presence of voltage at the input clamps 

   power supply to the motor 

—

 Check that the power supply cable is not interrupted. 

   (the power supply cable must be replaced 
   by an authorised technician)

—

 Check the fuses on the control unit

Incorrect regulation 
of the slowing point

—

 Repeat the programming of work times, paying attention to set 

slowing at no less than 50÷70cm from the stop.

No voltage to the 
control unit

—

 Check the network fuse and the presence of network voltage

—

 Check the network voltage -if present-

Meeting the stops 
makes movement 
reverse

Slowing speed set with 
"SLOW" potentiometer 
too low

—

 INCREASE THE "RALL" POTENTIOMETER: the "RALL" 

potentiometer, as well as the speed also decreases the power to 
the motor. For this reason a regulation that is too low can cause 
the gate to stop before reaching the mechanical stops. This stop 
also depends on the external environmental features, which vary 
greatly between summer and winter and between the first hours 
of the day with respect to the central hours. For this reason the 
gate may stop occasionally.

   Repeat work times programming by setting a quicker speed with 

the "RALL” potentiometer. 

The gate 
occasionally does 
not complete the 
entire slowing 
period, but blocks 
before

Intervention of the
amperometeric 
control

During movement 
and normal speed
the gate inverts 
movement

The motor moves
with difficulty

Insufficient motors 
power supply

—

 THE POWER SUPPLY CABLES TO THE MOTORS MUST 

HAVE ADEQUATE SECTION: we recommend cables measuring 

2

2.5mm  for 24vdc motors. cables with smaller section cause 
large voltage drops that make the motor speed force decrease, 
especially on the motor furthest away from the control unit

—

 INCREASE THE "AMP" POTENTIOMETER: the "AMP" 

potentiometer regulates the amperometeric control intervention, 
which intervenes every time that the gate stops moving for a brief 
period of time due to external factors-such as gusts of wind for 
example-. Therefore, in the case of particularly windy areas, it is 
recommended to exclude the amperometric control by taking the 
potentiometer to MAX

—

 INCREASE THE "VELOC" POTENTIOMETER: the "VELOC" 

potentiometer regulates the speed of the motors, decreasing the 
voltage. check the correct functioning by taking the 
potentiometer to MAX

C

R

/4

1

/2

4

 I

  

E

  

  

0

3

  

1

2

  

  

1

1

0

3

2

1

  

A

4

V

f/

-I

S

 C

R

4

1

-2

4

-E

Intervention of the 
amperometric control

—

 INCREASE THE "AMP" POTENTIOMETER: the "AMP" 

potentiometer regulates the amperometeric control intervention, 
which intervenes every time that the gate stops moving for a brief 
period of time due to external factors-such as gusts of wind for 
example-. therefore, in the case of particularly windy areas, it is 
recommended to exclude the amperometric control by taking the 
potentiometer to MAX

E L E T T R O N I C A        P A D O V A 

I

S

IN

C

E

 1

9

6

5

M A D E   I N   I T A L Y
VIA ENRICO FERMI, 22
35020 LEGNARO - PADOVA
I   T   A   L   I   A

PHONE           +39 049 79 08 58
FAX               +39 049 88 30 529

E-MAIL   [email protected]
WEB        www.serai.com

TERMS OF GUARANTEE

The company reserves the right to make modifications to the equipment without prior notice thereof. SERAI products are covered by a standard guarantee with a term of 24 months. 
Coverage starts on the date on which the tax document constituting proof of purchase is issued and guarantee services shall be provided on the company's premises at Legnaro - PD - 
or at the Authorised Service Centres. Carriage costs shall be borne by the Customer. 

CE CONFORMITY DECLARATION

SERAI spa declares that the product CR/41/24  has   been desifned and manufactured according to the above mentioned directives and standards

WEEE DIRECTIVE 2002/96/EC

This appliance was manufactured after 13/08/2005. To protect the environment: when the equipment is no longer needed, take it to a special WEEE (Waste Electric and 
Electronic Equipment) collection centre. Do not dispose of it with normal household waste.

Содержание CR/41/24

Страница 1: ...hibits the realisation of these types of plants by unqualified staff On realisation of its own products SERAI has respected the following Reference Directives for CE marking machinery 2006 42 EEC low...

Страница 2: ...en the lid from the opposite side proceed as follows ATTENTION This operation must be carried out before fixing the container to the wall Insert a flat tip screwdriver into the fixing recess of the hi...

Страница 3: ...le to the rest of the system to a minimum The control unit must be fixed via the cable passage holes facing downwards NO NO YES 6 8 mm Recommendations for connections in general rooms 1 Upstream from...

Страница 4: ...meter at maximum the amperometric control is excluded RALL POTENTIOMETER speed regulation during the slowing phase with the potentiometer at maximum slowing is excluded VELOC POTENTIOMETER regulation...

Страница 5: ...ontrol for electric lock SERAI M 83 1 With SW2dip2 ON control with the gate open indicator light function Input for the connection of the antenna for the built in receiver 33 BRAIDING EARTH 34 ANTENNA...

Страница 6: ...ter ATTENTION in this case there may be difficulties on start up if the force is regulated low 1 2 3 ON 4 1 2 3 ON 4 1 2 3 ON 4 1 2 3 ON 4 CLAMPS 11 12 FUNCTIONING MODE Open gate indicator light outpu...

Страница 7: ...essary to terminate the wing run with a certain approximation always slowing in the programmed point ATTENTION The lack of power supply to the circuit board network or battery causes the loss of the m...

Страница 8: ...key P2 WORK down until M1 starts When Motor M1 should start slowing we recommend at least 50cm before the stop press key P2 WORK The motor M1 slows down ATTENTION skip this point if slowing has been e...

Страница 9: ...s is set by regulating the AMP potentiometer The intervention of the amperometric control can be more or less rapid depending on the sensitivity set with the SW3 jumper The gate inverts movement for a...

Страница 10: ...2 OG 04 as pedestrian control the others do not have to be memorised OG 02 and OG 04 just set the micro switches in the same sequence as that memorised LEARNING START CODE With the control unit powere...

Страница 11: ...ALL AMP ON 1 2 4 3 SW1 ON 1 2 4 3 SW2 25 26 F2 F2 F3 F3 F1 F1 F4 F4 SW3 LED DL6 DL1 PED DL2 START DL3 STOP DL4 FOTO DL5 FOTOAP DL7 COSTA PAUSA LAVORO PROGR BATTERY Power supply transformer 230 20 Vac...

Страница 12: ...ntiometer regulates the amperometeric control intervention which intervenes every time that the gate stops moving for a brief period of time due to external factors such as gusts of wind for example T...

Отзывы: