Technical Specification & Installation 

Sentinel Kinetic MVHR Installation & Commissioning 

13

 

 

Table 1: Terminal Connections 

 

 

 

Name 

Description 

S/W1 

Switch 1 

With link fitted on J4 - activates volt-free contact for sensor input 
b and - terminals 
 

With Vent-Wise PCB fitted to J4 - enables Vent-Wise sensor input 

 

Note do not fit standard sensors or Volt- free switch contact in this 
mode. 

S/W2 

Switch 2 

S/W3 

Switch 3 

SW4 

Switch 4 

Volt-free contact for sensor input b and 

– terminals 

 

With Vent-Wise PCB fitted to J4 - enables Vent-Wise momentary switch 
input 

SW5 

Switch 5 

Volt-free contact for sensor input b and - terminals 

P1 0-10V 

Proportional 1  

A 24 V DC sensor supply is output between the + and - terminals.  
A 10 V proportional sensor input is received between S and - terminals 

P2 0-10V 

Proportional 2 

A 24 V DC sensor supply is output between the + and - terminals.  
A 10 V proportional sensor input is received between S and - terminals 

LED 

Red Light Emitting Diode 
Output 

A 5 V LED driving signal output between the + and 

– terminals that 

enables remote indication of a unit fault. See the Control Panel for fault 
code (se

Service/Fault Code Screens

 on page 34). 

Mains Live 

220-240 V AC, 50 Hz input 

Mains Neutral 

220-240 V AC, 50 Hz input 

EARTH 

Mains Earth 

Earthing connector 

LS 

Switched Live 

220-240 V AC, 50 Hz input 

Connect the Power Supply 

WARNINGS 

1.  MAINS SUPPLY VOLTAGES (220-240 V AC) ARE PRESENT IN THIS EQUIPMENT WHICH MAY CAUSE 
DEATH OR SERIOUS INJURY BY ELECTRIC SHOCK. ONLY A QUALIFIED ELECTRICIAN OR INSTALLER 

SHOULD CONNECT THE POWER SUPPLY TO THIS UNIT. 

2.  THIS UNIT MUST BE CORRECTLY EARTHED.  

This unit is designed for operation from a single-phase alternating current source (220-240 V AC). A 2 m cable is 
connected internally to the unit for connection to a switched fused spur. 

To connect the power supply: 

1.

 

Ensure the local AC power supply is switched off. 

One end of the power cable supplied is already connected to the unit. 

 

Connect the other end of the cable to the switched fused spur. 

Use cable clamps and clips to secure the cable, as appropriate. 

Connecting a Boost (Light) Switch 

A Switched Live (LS) may be used to boost the airflow when a light is turned on, for instance in a bathroom or 
kitchen.  

Power supplied to the unit via a Switched Fused Spur must be supplied via the same circuit as the LS connecti

Содержание 447801

Страница 1: ...t Axia Limited All rights reserved Sentinel Kinetic 200Z 200ZH 300Z 300ZH Installation Commissioning Model Stock Ref N 200Z 448733 200ZH 449540 300Z 447801 300ZH 449536 PLEASE RETAIN THESE INSTRUCTION...

Страница 2: ...RILLE ASSOCIATED WITH THE UNIT IS SITED IN A ROOM CONTAINING A FUEL BURNING APPLIANCE THE INSTALLER MUST ENSURE THAT AIR REPLACEMENT IS ADEQUATE FOR BOTH APPLIANCES 12 CERTAIN APPLICATIONS MAY REQUIRE...

Страница 3: ...oning 19 Overview 19 Commissioning Screens 20 Maintenance 30 Filter Maintenance 30 12 Monthly Maintenance 30 Spares 33 Troubleshooting 34 Diagnosing a Problem 34 Appendix Options and Accessories 35 CO...

Страница 4: ...he set indoor temperature i e you need the room heating and the outdoor air is warmer than the actual room temperature i e the outdoor air could heat your room then the SBP will open and the unit will...

Страница 5: ...elow See Graph below Power AC Voltage Input 220 240 V AC single phase AC Frequency Input 50 Hz nominal Supply Fuse 3 A located in fused spur Product Fuse 2 A located on main PCB Rated Power 150W max 1...

Страница 6: ...unting brackets and product documentation Lift and Move the Unit Safely Check the weight of the unit that you are installing Always use appropriate lifting techniques and appliances when moving heavy...

Страница 7: ...nting Fix the 2 Brackets to the ceiling the fixings must be suitable for the surface type intended concrete wood they must also be compatible for the units weight 200 Z ZH 26Kg 300Z 300ZH 38Kg 200Z 20...

Страница 8: ...ly tighten Leave approximately a half turn loose on each of the fixings This will allow each bracket to be moveable until final fitting of the unit and makes any adjustments easier while installing th...

Страница 9: ...e configuration 32mm 22mm waste For installations in a ceiling void where it is too shallow for a traditional U Trap configuration Our recommendation is to use a HepVO inline waste valve and Tundish A...

Страница 10: ...om Airflow Intake Air from atmosphere Airflow Exhaust Air to atmosphere Attaching the ducting 1 Always use a short piece of flexible ducting 100 150mm long extended to its full length when connecting...

Страница 11: ...end user or used for commissioning the unit 2 Fit the 15 metre Remote Control cable plug into the cable socket fitted to the Heat Recovery Unit 3 Connect the cable assembly to the Remote Control termi...

Страница 12: ...1 3 can be connected to be switched by a current detector for example detecting a hob being switched on or a temperature sensor for example detecting the flow of hot water Terminal 4 can be used in co...

Страница 13: ...f a unit fault See the Control Panel for fault code see Service Fault Code Screens on page 34 L Mains Live 220 240 V AC 50 Hz input N Mains Neutral 220 240 V AC 50 Hz input EARTH Mains Earth Earthing...

Страница 14: ...Turn the power off at the mains supply isolator Wired Remote Control Display Display Normal Airflow 30 Buttons Four buttons on the Control Unit provide the controls for configuring and monitoring the...

Страница 15: ...a percentage of the unit s maximum flow Airflow Units Wireless Control Screen Not available Wireless Control Not Fitted Humidity Sensor Screen The Humidity Sensor screen displays whether the humidity...

Страница 16: ...n be triggered from the wireless transmitter boost switch If the installation has switch sensors is wired to the lighting has Vent Wise sensors Vent Wise momentary switch or if the internal time switc...

Страница 17: ...t Clock Screen From the Normal Airflow screen simply press the button once to access the Set Clock screen The Set Clock Control screen enables you to change the clock settings The clock retains its se...

Страница 18: ...o on Indoor Temp 25 C Outdoor Temp Screen From the Normal Airflow screen simply press the button until the Indoor Temp is displayed Press button to choose the required temperature and then press butto...

Страница 19: ...ooting on page 34 Follow good practice when commissioning the unit Ensure that the system is installed according to the system designers intent incorporating any acoustic ducting that all joints are a...

Страница 20: ...ly 20 Low Extract 20 Ckr Hood Supply 30 Ckr Hood Extract 100 Boost Overrun 15 m Boost Delay 00 m Boost On Off Mon1 00 00 00 00 Boost On Off All Set Humidity Sensor Off Normal On Off Mon Normal On Off...

Страница 21: ...a security PIN code has been previously set this screen will display Enter the PIN using and buttons Security PIN Note 1 Whilst displaying the Low Normal Boost Supply Low Normal Boost Extract screens...

Страница 22: ...ormal speed cannot be set below Low speed or above Boost speed setting Normal Extract 30 Low Supply Screen The Low Supply screen enables you to set the Low airflow speed for the Supply fan in order to...

Страница 23: ...00 m Boost On Off Screen The Boost On Off screen enables you to set a time for boost to be activated for each day of the week You can set up to three On Off times per day shown as Day1 Day2 and Day3 I...

Страница 24: ...2 sec will copy yesterday s times to today Setting finishes when the last off minutes for Sun are accepted at which point the screen will now show All Set or holding the button for 3 seconds Normal O...

Страница 25: ...e Boost Limit the unit runs at boost airflow Between these limits the unit runs at a proportional airflow Proportional 1 Humidity For a humidity sensor a percentage value must be entered for boost and...

Страница 26: ...h three sensors will run hot to the touch albeit well below its maximum temperature If any input is shorted e g used with switch the board will overheat and shut down Nominal trip level is with the Lo...

Страница 27: ...for 15 minutes hour and run for 45 depending on the temperature below 0 C If the supply air temperature is 20 C or below the supply fan switches off and the extract fan continues to run at reduced ra...

Страница 28: ...off for example in conjunction with a smoke alarm No changes may be made to this screen BMS 00 The Security PIN screen enables you top set a four digit personal identification number PIN to access th...

Страница 29: ...off inactive Normal On Off All days set to 0 00 on 00 00 off inactive Set Service No Not set Humidity 70 Proportional 1 Humidity Boost Normal 60 CO2 Boost 2000 ppm Normal 1000 ppm Temperature Boost 2...

Страница 30: ...sing a vacuum cleaner if necessary 3 Replace the filters and cover plates 4 Reset the automatic message press and hold the and buttons for 5 seconds 12 Monthly Maintenance Item Action Fan Filters Inte...

Страница 31: ...te the mains power supply and remove the Filter access Panels and Filters Undo the securing screws and remove the Cover Stage 2 Loosen the Condensate Pipe Jubilee Clip and remove Pipe from Condensate...

Страница 32: ...Caution Keep the Tray as horizontal as possible as this may contain condensate Stage 5 Remove the two Heat Exchanger fixing Brackets and Heat Recovery Cell Note Take care when removing the Heat Recove...

Страница 33: ...d attention is retained in re applying all fixings to their previous locations Spares The following spares can be ordered from Vent Axia Description Part No 200Z 200ZH Part No 300Z 300ZH Filters 2 per...

Страница 34: ...For assistance contact the service provider and quote the fault code number The following fault codes numbers may be displayed Code numbers are added together if more than one is detected Table 4 Faul...

Страница 35: ...ally depending on the temperature and relative humidity levels in the extracted air whilst avoiding nuisance tripping at night time when temperatures drop and relative humidity naturally rises The uni...

Страница 36: ...not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your original supplier or nearest Ven...

Отзывы: