Technical Specification & Installation
Sentinel Kinetic MVHR Installation & Commissioning
13
Table 1: Terminal Connections
Name
Description
S/W1
Switch 1
With link fitted on J4 - activates volt-free contact for sensor input
b and - terminals
With Vent-Wise PCB fitted to J4 - enables Vent-Wise sensor input
Note do not fit standard sensors or Volt- free switch contact in this
mode.
S/W2
Switch 2
S/W3
Switch 3
SW4
Switch 4
Volt-free contact for sensor input b and
– terminals
With Vent-Wise PCB fitted to J4 - enables Vent-Wise momentary switch
input
SW5
Switch 5
Volt-free contact for sensor input b and - terminals
P1 0-10V
Proportional 1
A 24 V DC sensor supply is output between the + and - terminals.
A 10 V proportional sensor input is received between S and - terminals
P2 0-10V
Proportional 2
A 24 V DC sensor supply is output between the + and - terminals.
A 10 V proportional sensor input is received between S and - terminals
LED
Red Light Emitting Diode
Output
A 5 V LED driving signal output between the + and
– terminals that
enables remote indication of a unit fault. See the Control Panel for fault
code (see
on page 34).
L
Mains Live
220-240 V AC, 50 Hz input
N
Mains Neutral
220-240 V AC, 50 Hz input
EARTH
Mains Earth
Earthing connector
LS
Switched Live
220-240 V AC, 50 Hz input
Connect the Power Supply
WARNINGS
1. MAINS SUPPLY VOLTAGES (220-240 V AC) ARE PRESENT IN THIS EQUIPMENT WHICH MAY CAUSE
DEATH OR SERIOUS INJURY BY ELECTRIC SHOCK. ONLY A QUALIFIED ELECTRICIAN OR INSTALLER
SHOULD CONNECT THE POWER SUPPLY TO THIS UNIT.
2. THIS UNIT MUST BE CORRECTLY EARTHED.
This unit is designed for operation from a single-phase alternating current source (220-240 V AC). A 2 m cable is
connected internally to the unit for connection to a switched fused spur.
To connect the power supply:
1.
Ensure the local AC power supply is switched off.
One end of the power cable supplied is already connected to the unit.
Connect the other end of the cable to the switched fused spur.
Use cable clamps and clips to secure the cable, as appropriate.
Connecting a Boost (Light) Switch
A Switched Live (LS) may be used to boost the airflow when a light is turned on, for instance in a bathroom or
kitchen.
Power supplied to the unit via a Switched Fused Spur must be supplied via the same circuit as the LS connecti