Commissioning
Sentinel Kinetic MVHR Installation & Commissioning
23
Boost Overrun Screen
The Boost Overrun screen enables you to set a time
period for the fans to boost airflow (in minutes) after the
light switch (LS input) is turned off. It will then return to
normal airflow.
Selectable range: minimum =
00,
maximum =
25
,
default =
15
.
Boost Overrun screen does not function for inputs
S/W1 to S/W3 and SW4, SW5
Boost Overrun
15 m
Boost Delay Screen
The Boost Delay screen enables you to set the time
delay (in minutes) from the light switch (LS input) being
switched on to the airflow boost being activated. This is
used to prevent the unit from boosting unnecessarily
when the light switch is switched on for short periods.
Selectable range: min. =
00
, max. =
10,
default =
00
.
Boost Delay
00 m
Boost On/Off Screen
The Boost On/Off screen enables you to set a time for
boost to be activated for each day of the week.
You can set up to three
On
/
Off
times per day, shown
as
Day1
,
Day2
and
Day3
. If
On
and
Off
times are the
same, the unit will not change speed.
On
time cannot be set earlier than a previous off time,
Likewise,
Off
time cannot be set earlier than a previous
On
time.
To set a weekly schedule:
Setting starts at
Mon1
and uses
to show, by
flashing, which item is available for adjustment with the
and
buttons (a
→
b
→
c
→
d
→
e
→
Mon2
and
so on).
Mon1 10:01 11:11
↑
↑
↑
↑
↑
a b c d e
When
Day
flashes, pressing
(> 2 sec) will copy
yesterday
’s times to today.
Setting finishes when the last off minutes for
Sun3
are
accepted, at which point the screen will now show
All Set
or holding the
button for 3 seconds.
Boost On Off
Mon1 00:00 00:00
Boost On Off
All Set
(
Day
)
(
Day
)
(
On
)
(
On
)
Repeat for
Off
Repeat for each
Day
.
Note: if same
times are used
on subsequent
days,
will
copy times
found.