MOUNTING INSTRUCTIONS IN STEPS

Before you start mounting the STRS1, read carefully 

Safety and Precautions”

 and 

follow these steps. Choose a smooth solid surface for installation (a wall, panel, 
etc.).

Follow these steps:

1. 

 Unscrew the front cover and open the enclosure. Mind the wires that connect 
the rotary switch with the autotransformer or with the printed circuit board, 
depending on the product version. 

2. 

 Fix the unit onto the wall or panel using the provided screws and dowels. Mind the 
correct mounting position and unit mounting dimensions. (See

 Fig. 1

 

Mounting 

dimensions

 and 

Fig. 2

 

Mounting position

.)

3. 

 Pay attention to the following instructions in order to minimize the operating 
temperature:

3.1 

 Respect the distances both between the wall / ceiling and the device and 
between  two devices as shown in 

Fig. 2. 

In order to ensure sufficient 

ventilation of the controller, clearance on every side has to be maintained.

3.2 

 When installing the device, please keep in mind that the higher you install  
it, the warmer the device will get. For example, in a technical room the 
correct installation height can be of great importance. 

3.3 

 If maximum ambient temperature cannot be adhered to, please provide 
extra forced ventilation / cooling. 

Not respecting the abovelisted rules can reduce service life and relieves the 

manufacturer of any responsibilities.

Fig. 1 Mounting dimensions 

Fig. 2 Mounting position

A

C

B

E

D

Article code

A

[mm]

B

[mm]

C

[mm]

D

[mm]

E

[mm]

STRS1-15L22

115

205

100

98

140

STRS1-22L22

115

205

100

98

140

STRS1-25L22

170

255

140

155

194

STRS1-35L22

170

255

140

155

194

STRS1-50L22

170

255

140

155

194

STRS1-75L22

200

305

140

183

236

Correct

Incorrect

  50 mm

  50 mm

  75 mm

  50 mm

Wall

4. 

 Insert the cables through the cable glands and do the wiring according to the 
wiring diagram (see 

Fig. 3

) while adhering to the information from section 

Wiring and connections

” above. 

4.1 

Connect the power supply lines;

4.2 

Connect the motor(s);

4.3 

 If applicable, connect the unregulated output. It can be used to supply a 
230 VAC valve, lamp, etc. when the knob is not at ‘0’ position (see 

Table 1

 

below).

230 VAC TRANSFORMER 
CONTROLLER WITH TK

STRS1

Содержание STRS1 Series

Страница 1: ...Mounting and operating instructions 230 VAC TRANSFORMER CONTROLLER WITH TK POWER RANGE 1 5 7 5 A STRS1 ...

Страница 2: ...CT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 7 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 230 VAC TRANSFORMER CONTROLLER WITH TK STRS1 ...

Страница 3: ...ronment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting ...

Страница 4: ...20 mm F T 4 0 A H STRS1 35L22 3 5 5 20 mm F T 5 0 A H STRS1 50L22 5 0 5 20 mm F T 5 0 A H STRS1 75L22 7 5 5 20 mm F T 12 5 A H INTENDED AREA OF USE Speed control of voltage controllable 230 VAC single phase motors For indoor use only TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current depends on the version see article codes Unregulated output 230 VAC TK for thermal protection of ...

Страница 5: ...y neutral N1 Unregulated output neutral L1 Unregulated output phase U Regulated output to motor line N Regulated output to motor neutral TK Thermal contact for motor protection TK STRS1 35L22 STRS1 50L22 and STRS1 75L22 M Power supply phase 230 VAC 50 60 Hz N Power supply neutral L1 Unregulated output phase N Regulated output to motor neutral U Regulated output to motor line TK Thermal contact for...

Страница 6: ...3 2 When installing the device please keep in mind that the higher you install it the warmer the device will get For example in a technical room the correct installation height can be of great importance 3 3 If maximum ambient temperature cannot be adhered to please provide extra forced ventilation cooling Not respecting the abovelisted rules can reduce service life and relieves the manufacturer o...

Страница 7: ... sure the transformer controller can operate normally consider an isolating switch 10 Turn the knob into the relevant position to adjust the output voltage Optional settings The standard configuration of the output voltages is as indicated in Table 1 below However because more than 5 output voltages are available it is possible to adjust the 5 steps by changing the internal wiring Table 1 Voltage ...

Страница 8: ...ealth Take the relevant safety measures ATTENTION Disconnect and confirm that there is no live current flowing to the unit before servicing ATTENTION Avoid exposing the controller to direct sunlight TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alte...

Страница 9: ...www sentera eu MIW STRS1 15 75 LXX EN 000 21 09 2018 9 9 back to the table of contents 230 VAC TRANSFORMER CONTROLLER WITH TK STRS1 ...

Отзывы: