background image

www.sentera.eu

MIW-STRS1-15-75-LXX-EN-000 - 21 / 09 / 2018

5 - 9

back to the table of contents

OPERATIONAL DIAGRAM

L22 series

0

1

2

3

4

5

230

190

170

140

110

U [VAC]

L1

Knob position

Regulated output

 (U)

Unregulated output

 (L1)

WIRING AND CONNECTIONS

STRS1-15L22, STRS1-22L22 and STRS1-25L22

Pe 

Earth terminal

L

Power supply, phase (230 VAC / 50—60 Hz)

N

Power supply, neutral

N1

Unregulated output, neutral 

L1

Unregulated output, phase

U

Regulated output to motor, line

N

Regulated output to motor, neutral

TK

Thermal contact for motor protection 

TK

STRS1-35L22, STRS1-50L22 and STRS1-75L22

M

Power supply, phase (230 VAC / 50—60 Hz)

N

Power supply, neutral

L1

Unregulated output, phase

N

Regulated output to motor, neutral

U

Regulated output to motor, line

TK

Thermal contact for motor protection 

TK
Pe

Earth terminal

ATTENTION

Make sure you use cables with an appropriate diameter.

230 VAC TRANSFORMER 
CONTROLLER WITH TK

STRS1

Содержание STRS1 Series

Страница 1: ...Mounting and operating instructions 230 VAC TRANSFORMER CONTROLLER WITH TK POWER RANGE 1 5 7 5 A STRS1 ...

Страница 2: ...CT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 WIRING AND CONNECTIONS 5 MOUNTING INSTRUCTIONS IN STEPS 6 VERIFICATION OF INSTALLATION 7 TRANSPORT AND STORAGE 8 WARRANTY AND RESTRICTIONS 8 MAINTENANCE 8 230 VAC TRANSFORMER CONTROLLER WITH TK STRS1 ...

Страница 3: ...ronment is as dry as possible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts Always disconnect the power supply before connecting ...

Страница 4: ...20 mm F T 4 0 A H STRS1 35L22 3 5 5 20 mm F T 5 0 A H STRS1 50L22 5 0 5 20 mm F T 5 0 A H STRS1 75L22 7 5 5 20 mm F T 12 5 A H INTENDED AREA OF USE Speed control of voltage controllable 230 VAC single phase motors For indoor use only TECHNICAL DATA Supply voltage 230 VAC 50 60 Hz Maximum motor current depends on the version see article codes Unregulated output 230 VAC TK for thermal protection of ...

Страница 5: ...y neutral N1 Unregulated output neutral L1 Unregulated output phase U Regulated output to motor line N Regulated output to motor neutral TK Thermal contact for motor protection TK STRS1 35L22 STRS1 50L22 and STRS1 75L22 M Power supply phase 230 VAC 50 60 Hz N Power supply neutral L1 Unregulated output phase N Regulated output to motor neutral U Regulated output to motor line TK Thermal contact for...

Страница 6: ...3 2 When installing the device please keep in mind that the higher you install it the warmer the device will get For example in a technical room the correct installation height can be of great importance 3 3 If maximum ambient temperature cannot be adhered to please provide extra forced ventilation cooling Not respecting the abovelisted rules can reduce service life and relieves the manufacturer o...

Страница 7: ... sure the transformer controller can operate normally consider an isolating switch 10 Turn the knob into the relevant position to adjust the output voltage Optional settings The standard configuration of the output voltages is as indicated in Table 1 below However because more than 5 output voltages are available it is possible to adjust the 5 steps by changing the internal wiring Table 1 Voltage ...

Страница 8: ...ealth Take the relevant safety measures ATTENTION Disconnect and confirm that there is no live current flowing to the unit before servicing ATTENTION Avoid exposing the controller to direct sunlight TRANSPORT AND STORAGE Avoid shocks and extreme conditions stock in original packing WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing Any modifications or alte...

Страница 9: ...www sentera eu MIW STRS1 15 75 LXX EN 000 21 09 2018 9 9 back to the table of contents 230 VAC TRANSFORMER CONTROLLER WITH TK STRS1 ...

Отзывы: