4. 

Do the wiring according to the wiring diagram (see 

Fig. 4

).

Fig. 4 Wiring and connections

Analog / modulating 

output

Power supply

RMFPF-2R: 18—34 VDC

RMFPG-2R:  18—34 VDC / 

15—24 VAC ± 10% 

Modbus RTU

5. 

Put back the cover snap it in.

6. 

Switch on the mains supply.

5. 

Optional settings

 If your unit is the first or the last unit on the Modbus RTU network (see 

Example 1

 

and 

Example 2

), enable the NBT resistor via 3SModbus or Sensistant. If your device 

is not an end device, leave the NBT disabled (default Modbus setting).

 

Example 1

Example 2

Slave 1

RX

ТX

NBT

NBT

NBT

Slave 2

Master

Slave n

Slave 2

Slave 1

RX

ТX

NBT

NBT

Master

Slave n

ATTENTION

If an AC power supply is used with any of the units on a Modbus network, the 
GND terminal should NOT BE CONNECTED to other units on the network or 
via the CNVT-USB-RS485 converter. This may cause permanent damage to the 
communication semiconductors and / or the computer!

ATTENTION

Do not exceed the maximum power supply rating! Measure before installation! 
Unregulated 24 VAC supply units provide higher nominal output voltage and 
activate the integrated fuse protection.

 

ATTENTION

We advise you not to use G and F-type articles together on the same network. If 
G and F-type articles are used together on the same network, make sure you use 
separate power supplies for both types. Always connect different article types to 
separate AC transformers or use the same article version.

 

CAUTION

Do not expose to direct sunlight!

RMFPX-2R

MULTIFUNCTIONAL 
ROOM CONTROLLER

Содержание RMFPX-2R

Страница 1: ...Mounting and operating instructions RMFPX 2R MULTIFUNCTIONAL ROOM CONTROLLER ...

Страница 2: ...ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 MODBUS REGISTER MAPS 9 TRANSPORT AND STORAGE 11 WARRANTY AND RESTRICTIONS 11 MAINTENANCE 11 RMFPX 2R MULTIFUNCTIONAL ROOM CONTROLLER ...

Страница 3: ...ossible avoid condensation All installations shall comply with local health and safety regulations and local electrical standards and approved codes This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions Avoid contacts with energised electrical parts always treat the product as if it is live Always disconnect the power suppl...

Страница 4: ...50 kΩ 0 20 mA max load 500 Ω RL 500 Ω PWM open collector type PWM Frequency 1 kHz min load 50 kΩ RL 50 kΩ PWM voltage level 3 3 or 12 VDC Selectable temperature range 0 50 C Selectable relative humidity range 5 85 Selectable CO2 range 0 2 000 ppm Removable sensor CO2 element for easy calibration and verification Compatible with SSCDM Sentera Sensor Calibration Device 3 LEDs for status indication A...

Страница 5: ...1 65 EC OPERATIONAL DIAGRAMS AO1 max range AO1 min range 60 40 100 0 rH Min range 0 5 0 CO2 Min range CO2 Max range Max Min T Min range T Max range rH Max range AO1 50 85 2 000 rH T C CO2 ppm Note The output changes automatically depending on the highest T rH or CO2 values i e the highest of three output values controls the output See the green line in the operational diagram above WIRING AND CONN...

Страница 6: ... 2 Insert the cables through the opening on the rear plate See Fig 2 Mounting dimensions 3 Using suitable fastening materials not supplied position the room sensor at least 1 5 m from the floor When planning the installation allow enough clearance for maintenance and service Mount the sensor in a well ventilated area Mind the correct mounting position and unit dimensions See Fig 2 and Fig 3 Fig 1 ...

Страница 7: ...T Master Slave n ATTENTION If an AC power supply is used with any of the units on a Modbus network the GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT USB RS485 converter This may cause permanent damage to the communication semiconductors and or the computer ATTENTION Do not exceed the maximum power supply rating Measure before installation Unregulated 24 VAC sup...

Страница 8: ... at least 5 seconds to reset the Modbus communication parameters 1 2 3 4 5 Put a jumper onto pins 3 and 4 and restart the supply to enter bootloader mode LED indications 1 When the green LED is on the measured value temperature relative humidity or CO2 is between the minimum and maximum alert range values Fig 6 1 2 When the yellow LED is on the measured value temperature relative humidity or CO2 i...

Страница 9: ...1 when the measured value is outside the temperature alert values defined by holding registers 20 and 21 0 1 0 1 Measured temperature is OK Measured temperature is too high low 15 Relative humidity alert flag unsigned int Flag indicates that measured relative humidity is outside set alert values Set to 1 when the measured value is outside the relative humidity alert values defined by holding regis...

Страница 10: ... 0 ºC 22 Minimum relative humidity alert unsigned int Minimum relative humidity alarm value Min relative humidity range Max relative humidity alarm 50 200 20 0 rH 23 Maximum relative humidity alert unsigned int Maximum relative humidity alarm value Min relative humidity alarm Max relative humidity range 850 850 85 0 rH 24 Minimum CO2 alert unsigned int Minimum CO2 alarm value Min CO2 range Max CO2...

Страница 11: ...ublication relieve the manufacturer of any responsibilities The manufacturer bears no responsibility for any misprints or mistakes in this data MAINTENANCE In normal conditions this product is maintenance free If soiled clean with a dry or damp cloth In case of heavy pollution clean with a non aggressive product In these circumstances the unit should be disconnected from the supply Pay attention t...

Отзывы: