HOLDING REGISTERS
Data type
Description
Data
Default Values
1
Device slave address
unsigned int. Modbus device address
1—247
1
2
Modbus baud rate
unsigned int. Modbus communication baud rate
0—6
2
0 =
1 =
2 =
3 =
4 =
5 =
6 =
4.800
9.600
19.200
38.400
57.600
115.200
230.400
3
Modbus parity mode
unsigned int. Parity check mode
0—2
1
0 =
1 =
2 =
8N1
8E1
8O1
4
Device type
unsigned int. Device type
(Read only)
RMFPX-2R = 1106
5
HW version
unsigned int. Hardware version of the device
(Read only)
XXXX
0x0100 =
HW version 1.00
6
FW version
unsigned int. Firmware version of the device
(Read only)
XXXX
0x0100 =
FW version 1.00
7
Reserved, returns “0”
8
Output 1 overwrite
unsigned int. Enables the direct control over the output
0—1
0
0 =
1 =
Disabled
Enabled
9—10
Reserved, return “0”.
11
Output 1 type
unsigned int. Select analog / digital output type
1—3
1
1 =
2 =
3 =
1—10 VDC
0—20 mA
PWM
12—13
Reserved, return “0”.
14
Minimum temperature
range
unsigned int. Minimum value of the temperature range; cannot be
set higher than max. temperature range minus 5
º
C
0 — (Max. range — 50)
0
100 =
10,0 °C
15
Maximum temperature
range
unsigned int. Maximum value of temperature range; cannot be set
lower than min. temperature range plus 5
º
C
(Min. range + 50) – 500
500
500 =
50,0 °C
16
Minimum relative
humidity range
unsigned int. Minimum value of the rH range; cannot be set higher
than max. rH range minus 5
%
50 — (Max. range — 50)
50
200 =
20,0 % rH
17
Maximum relative
humidity range
unsigned int. Maximum value of rH range; cannot be set lower than
min. rH range plus 5%
(Min. range + 50) – 850
850
850=
85,0 % rH
18
Minimum CO
2
range
unsigned int. Minimum value of the CO
2
range; cannot be set higher
than max. CO
2
range minus 100 ppm
0 – (Max. range — 100)
400
1.000 =
1.000 ppm
19
Maximum CO
2
range
unsigned int. Maximum value of CO
2
range; cannot be set lower
than min. CO
2
range plus 100 ppm
(Min. range + 100) – 2.000
2.000
2.000 =
2.000 ppm
20
Minimum temperature
alert
unsigned int. Minimum temperature alarm value
Min. temperature range —
Max. temperature alarm
0
100 =
10,0
º
C
21
Maximum temperature
alert
unsigned int. Maximum temperature alarm value
Min. temperature alarm —
Max. temperature range
500
500 =
50,0
º
C
22
Minimum relative
humidity alert
unsigned int. Minimum relative humidity alarm value
Min. relative humidity range —
Max. relative humidity alarm
50
200 =
20,0 % rH
23
Maximum relative
humidity alert
unsigned int. Maximum relative humidity alarm value
Min. relative humidity alarm —
Max. relative humidity range
850
850 =
85,0 % rH
24
Minimum CO
2
alert
unsigned int. Minimum CO
2
alarm value
Min. CO
2
range — Max. CO
2
alarm
400
400 =
400 ppm
25
Maximum CO
2
alert
unsigned int. Maximum CO
2
alarm value
Min. CO
2
alarm — Max. CO
2
range
2.000
2.000 =
2.000 ppm
26
LED indication
unsigned int. LED indication related to one of the parameters
1—3
1
1 =
2 =
3 =
temperature
rH
CO
2
27
Internal voltage source
selection Output 1
unsigned int. Selection of internal voltage source for PWM output
0—1
0
0 =
1 =
3,3 VDC
12 VDC
28—29
Reserved, return “0”.
30
Modbus network resistor
termination (NBT)
unsigned int. Set device as ending the line or not by connecting
NBT
0—1
0
0 =
1 =
NBT disconnected
NBT connected
31
Output 1 overwrite value unsigned int. Overwrite value for output 1.
Active only if Holding
register 8 is set to 1
0—1.000
0
0 =
1.000 =
0 %
100 %
32—33
Reserved, return “0”.
34
Active level
unsigned int. The ambient light level above which ‘Active’ is
indicated in input register 6
0—32.000
100
1.000 =
1.000 lx
35
Standby level
unsigned int. The ambient light level below which ‘Standby’ is
indicated in input register 6
0—32.000
10
10 =
10 lx
36
Modbus registers reset
unsigned int. Resets Modbus Holding registers to default values.
When finished this register is automatically reset to ‘0’
0—1
0
0 =
1 =
Idle Reset Modbus
registers
37
CO
2
module self
calibration (ABC logic)
algorithm
unsigned int.
Enables or disables the CO
2
module self-calibration
algorithm. If enabled, the sensor will typically reach
its operational accuracy after 24 hours of continuous
operation. The sensor will maintain its accuracy given
that it is exposed to a reference level of 400 ppm CO
2
at least once in a 7 day period
0—1
1
0 =
1 =
Disabled
Enabled
38
Minimum output value
unsigned int. Sets minimum value of output signal in percentage
0—40
0
20 =
20 %
39
Maximum output value
unsigned int. Sets maximum value of output signal in percentage
60—100
100
60 =
60 %
40
Reserved, returns “0”.
If you want to find out more about Modbus over serial line, please visit:
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
RMFPX-2R
MULTIFUNCTIONAL
ROOM CONTROLLER