Input/output configuration
Page 84
FlexZone Product Guide
Input configuration procedure (Remote control mode)
1. Select the Aux Cfig tab on the UCM window.
2. From the Supervision drop down, select the desired supervision scheme for the input.
3. Select the Resistor 1 value, if applicable.
4. Select the Resistor 2 value, if applicable.
5. Set the Noise Tolerance, if required.
6. Set the Line Drop, if required.
7. Set the Filter Window.
8. Repeat this procedure if there is a second connected input.
9. Save the UCM configuration file and download the configuration changes to the processor.
Output relays
Output relay setup (Local control mode)
In Local control mode, the four relays are setup via the Local Aux Control Activation check boxes
to report alarm conditions. The relays are then controlled by the processor to activate on the user-
specified conditions. The relays remain active for an event’s duration or for the selectable relay
Active Time, whichever is longer.
1. Use the Output selection arrows to select a relay.
2. Specify the Hold/Active Time parameter.
3. Specify the conditions from the Local Aux Control Activation field under which this relay will
activate.
4. Repeat this procedure for the other relays.
5. Save the UCM configuration file and download the configuration changes to the processor.
Output relay setup (Remote control mode)
In Remote control mode, the relays are controlled by the host SMS to operate auxiliary equipment
as output control points (e.g., to activate lights, doors, sirens, CCTV equipment, etc.). You
configure the relays response to commands from the host computer. You can configure the relays
as latching (ON by command, OFF by command) or in flash mode (ON-OFF-ON-OFF etc. by
command, OFF by command) or in pulse mode (ON for a period, then OFF). For flash and pulse
modes, the ON-OFF time duration is configurable.
1. Use the Output selection arrows to select a relay.
2. Select the type of relay Activation (latching, or flash mode, or pulse mode).
3. Select the Hold/Active Time parameter, if applicable.
4. Select the Inactive Time parameter, if applicable.
5. Repeat this procedure for the other relays.
6. Save the UCM configuration file and download the configuration changes to the processor.
Note
The four outputs on the ROC function the same as the four outputs on
the processor. Follow the directions for setting up the processor’s relay
outputs to setup the outputs on the ROC (local or remote control).
Note
To assign relays to specific zones, see
Linking cable segments to relays
(local control mode) on page 85
.