Processor calibration
Page 80
FlexZone Product Guide
1. Below the Segment Setting window, select the Split button.
The selected cable segment is divided into 2 sections, the white section is the currently
selected Segment.
2. Use the Range (m) spin control to enter the meter at which this cable segment begins.
3. Use the Zone: spin control to assign the segment to an alarm Zone (label the zone according
to the site plan; more than one cable segment can be assigned to an alarm zone).
4. Repeat this procedure to define each cable segment and zone, as specified in the site plan.
5. Save the UCM file and download the configuration data to the processor.
6. Repeat this procedure for the B Side sensor cable.
Setting the endpoint of detecting cable
Use the results of the location tap testing to specify the end point of the detecting cable.
1. Select the last defined cable segment (the segment that includes the meter at which detection
ends).
2. Select the Split button.
3. Use the Range (m) spin control to enter the meter at which detection ends.
4. Use the spin controls to assign the last Segment to Zone 0.
5. Save the UCM file and download the configuration data to the processor.
6. Repeat this procedure for the B Side sensor cable.
Note
You can also drag the zone boundary to the appropriate point in the
profile window.
Note
Any sections of detecting cable that should NOT report alarms must be
assigned to Zone 0 (e.g., cable bypasses across gates).
Figure 87: Defining the end point of detecting cable
no Zone label for the segment beyond
2
4
3
the end point of detecting cable (Zone 0)
no Threshold for the segment beyond the end point