background image

WIRELESS WALL SWITCH 

& LOAD CONTROLLER

INSTALLATION & OPERATION INSTRUCTIONS

MODEL NUMBERS

DESCRIPTIONS

SWX-851-xx

WIRELESS WALL SWITCH LOAD CONTROLLER, 
120/277VAC, NO NEUTRAL REQUIRED

BASIC OPERATION 

A received wireless message indicating occupancy from one or more wirelessly linked 
sensors will trigger the unit’s integrated relay to close. When configured for Vacancy 
operation, lights must be initially switched on by pressing the unit’s button (or by pressing 
the ON button on a wirelessly linked wall station). Once closed, line voltage will flow 
through the relay and turn on the connected lighting load. This wall switch load controller 
maintains a master time delay that is reset every time a linked sensor reports occupancy. 
Lights will be switched off once there hasn’t been an occupancy message reported for the 
duration of the time delay. 

* xx = color (WH, IV, AL, GY)

SPECIFICATIONS 

ELECTRICAL

OPERATING VOLTAGE

120-277 VAC, Single Phase, 50/60 Hz

LOAD RATINGS

MAX:   800W @ 120VAC 

      1200W @ 277VAC 

MIN: None 

LOAD TYPES

LED Driver/Lamps 

CFL, Electronic/Magnetic Ballasts 

(Fluorescent) 

Tungsten (Incandescent)

ESD IMMUNITY

Tested to withstand electrostatic 

discharge without damage or  

memory loss.

SURGE IMMUNITY

Tested to withstand surge voltages 

without damage or loss of operation.

NON-VOLATILE MEMORY

Saves all settings even if power is 

disrupted.

ENVIRONMENTAL

OPERATING TEMP

32°F to 122°F (0°C to 50°C)

RELATIVE HUMIDITY

0-95% Non-Condensing, Indoor Use 

Only

OPERATION

OPERATING MODES

 Occupancy, Vacancy, Switch Disable

TIME DELAY OPTIONS

1, 5, 10, 15, 20, 30 min.

WIRELESS

RANGE

80’ line of site w/o obstruction (walls) 

40’ with obstruction (walls/floors)

FREQUENCY    

915 MHz ISM Band  

 

WIRELESS LINKING

Simple 3 sec. Push Button Process

SECURITY

All Wireless Data is Encrypted

PHYSICAL

SIZE

2.74”H x 1.68”W x 1.39”D 

(6.96 x 4.27 x 3.53 cm)                                               

<1” Wallbox Mounting Depth

WEIGHT 

4.5 oz

MOUNTING

Single Gang Switch Box

LED STATUS INDICATOR

Bi-color White & Blue

CODE COMPLIANCE

These load controllers can be used to 
meet ASHRAE 90.1, IECC, & Title 24 
energy code requirements.

OVERVIEW 

The 

SENSOR

WORX wireless wall switch load controller links to remote occupancy 

sensors and switches without low voltage wiring in order to provide automatic lighting 
control. Designed with contractors in mind, the unit is significantly shallower than typical 
wall controllers, resulting in less crowded wall boxes. Additionally, versatile wiring 
enables usage with or without a neutral connection and never requires a minimum load. 
This switch also matches the 

SENSOR

WORX family of wall switch occupancy sensors 

and 0-10V dimming wall switch sensors. All 

SENSOR

WORX products are proudly made 

in the USA.

FEATURES 

ELECTRICAL FEATURES

 

Ã

Accommodates Neutral (3-Wire) and No-Neutral (2-Wire) Installations

 

Ã

Electronically Timed Switching Ensures Long Relay Life

 

Ã

No Minimum Load or External Load Capacitor (MLC) Requirements

 

Ã

Meets Regulatory Guidelines for Current Leakage 

PHYSICAL FEATURES

 

Ã

Enclosure is 25-40% Shallower than Other Wall Controllers (< 1” Depth into 
Wallbox)

 

Ã

Self-Grounding Mounting Strap

 

Ã

Modern Look and Intuitive Easy-Tap Button

OPERATIONAL FEATURES

 

Ã

Pairs in Seconds with Wireless Sensors & Remote Wall Stations

 

Ã

Configurable Time Delays and Operational Modes (e.g. Occupancy, Vacancy, 
Switch Disable)

 

Ã

Blue Locator LED when Lights are Off

 

Ã

Settings are Adjustable Without Removing Cover Plate

 

Ã

Links with up to 30 sensors and/or switches

Содержание SWX-851 Series

Страница 1: ...40 with obstruction walls floors FREQUENCY 915 MHz ISM Band WIRELESS LINKING Simple 3 sec Push Button Process SECURITY All Wireless Data is Encrypted PHYSICAL SIZE 2 74 H x 1 68 W x 1 39 D 6 96 x 4 27 x 3 53 cm 1 Wallbox Mounting Depth WEIGHT 4 5 oz MOUNTING Single Gang Switch Box LED STATUS INDICATOR Bi color White Blue CODE COMPLIANCE These load controllers can be used to meet ASHRAE 90 1 IECC T...

Страница 2: ...ations where Neutral connection is available as well as installations where only Ground connection is present à If no neutral is present remove the white sleeve from the wire connect the now Green Yellow wire to Ground à Note either the white wire or green yellow wire must be connected The all green wire is just for safety BASIC WIRING WARNING TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING LI...

Страница 3: ...troller is quickly done via the following procedure Step 1 Enter pairing mode by holding down the wall switch s button for 3 seconds until the LED starts alternating blue and white then release Step 2 At the sensor or other remote device hold down the programming button for 3 seconds until the LED starts alternating blue and white Releasing will link the sensor with the switch in pairing mode see ...

Страница 4: ... saving during any step release button and wait until the unit double flashes blue ADDITIONAL NOTES ON OCCUPANCY TIME DELAY à By default every 60 seconds wireless sensors transmit a status message whether or not occupancy was detected during the previous period à Referred to as the sensor s heartbeat this period can be reduced to 30 seconds although this will decrease expected battery life à If a ...

Страница 5: ...he number of times equal to the current setting e g 3 times for Automatic On Occupancy Mode Following a short pause this blink back sequence will repeat 3x before exiting Interrupt blink back by pressing the button the number of times equal to the new desired setting e g 2 Vacancy Mode The LED will blink back white the new setting number as confirmation 6 To Save and Exit programming mode press an...

Страница 6: ...ton 7 times wait 2 seconds then press the button 3 times to disable location functionality or 2 times to enable 3 To Execute the command and Exit programming mode press and holding the button until the LED changes to blue then release The LED will then blink white twice as confirmation of success Note To Exit without saving during any step release button and wait until the unit double flashes blue...

Страница 7: ...s equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that ...