3.3.1.2. Network Connection - Setting the IP address of the FA 46 Vision Sensor
Before connecting the sensor in the network, check with the network administrator whether
the sensor’s address has already been assigned (default: 192.168.100.100 with subnet mask
255.255.255.0). This can otherwise cause network failure.The set IP address is to be noted on
the enclosed label. The label is then to be stuck on the sensor in a clearly visible place after
installation.
Network connection speed:
The sensor must only be operated with 100MBit/full-duplex when using VGA resolution and
SensoView.
Sensor’s IP still free:
Connect sensor to network and then set the sensor’s IP to match the PC according to the administrator’s specifica
-
tions, as follows.
Sensor IP already assigned:
1. First connect sensor and PC directly (see chapter 3.3.1.1) and set an authorised IP address in the sensor.
2. Connection via the network can then be carried out.
First ensure electrical connection (see chapter 3.2) and installation of PC software (see chapter 4 Commissioning)
have been completed.
To set the IP address on the FA 46 Vision Sensor, the following steps are to be carried out in the PC software:
1. Start SensoFind
2. Mark Sensor.
3. Set sensor’s new IP address with “Settings”.
This was assigned by the system administrator, see
fig. 9. The PC’s IP address is shown in the status
bar under the buttons.
4. Restart the sensor (disconnect power supply for 5
seconds).
5. Close SensoFind and restart,
6. Mark sensor and connect.
Fig. 9
155-01200
Fig. 10
155-01201
Modification of the standard gateway enables operation
in different sub-networks. Only alter this setting after
consultation with the administrator.
Automatic integration of a new computer or sensor in the existing network without
manual configuration is possible through DHCP. Normally, automatic supply of IP
address must only be set on the sensor, the client. When the sensor is started in the
network, it can obtain the IP address, net mask and gateway from a DHCP server.
Activation of DHCP mode is carried out via the “Settings” button by activating the
checkbox “DHCP“. As one and the same FA 46 can thus have different IP addres-
ses at different times, a sensor name must be attributed when activating the DHCP.
Should several FA 46s be in one network, different names must be used.
If a FA 46 with DHCP is switched on in a network without a DHCP server, the FA 46 automatically
sets the IP address to 192.168.0.65. This can be the case, e.g. in the case of power/server failure
or the restart of a system after shutdown as the DHCP server may boot slower than the FA 46.
Make sure that the FA 46 is only switched on when the DHCP server is available.