ENGLISH
Pag. 29
³
For the detectors’ power supply connection, we recommend using a 2-wire cable with
suitable section according to the distance and number of detectors.
³
Once the installation has been completed, verify that each detector reaches at least
12 Vdc.
5.8 Connection to relay board (optional)
During configuration of SMART S-IS detector it’s possible to associate alarm thresholds and
fault signal to the relay board.
Relay 1 is associated to Fault and Watch-dog. The remaining two are to be associated to two
outputs of the three pre-set alarm thresholds. Default relays associations are: threshold 2-re-
lay 2; threshold 3-relay 3.
Relays are not-memorised and they are not time-limited. The user cannot silence the alarm
manually, it will silence automatically when the its cause won’t be present anymore.
Figure 4) 3 relays board
JP9
JP6 JP4
RELAY
3
RELAY
2
RELAY
1
DL1 DL3 DL2 DL4 DL5
JP8
JP5
JP3
6
1
JP2: Relays connector
COM1
S1
COM2
S2
COM3
S3
1
1
1
1
1
JP2
JP1
JP4: security of relays
Closed (default): normallly not energized
Open: normally energized
JP9:
1-2 closed: relay 3 for alarm 2
2-3 closed (default): relay 3 for alarm 3
JP6:
1-2 closed: relay 2 for alarm 1
2-3 closed (default): relay 2 for alarm 2
JP3, JP5 and JP8: signal of relays 1, 2 and 3
1-2 closed: normally closed
2-3 chiusi (default): normally open
JP1: Main board connector
DL1 green LED - ON when the device is powered ON
DL2 yellow LED - ON when watchdog error
DL3 yellow LED - ON when fault
DL4 red LED - ON when alarm 1 or 2
DL5 red LED - ON when alarm 2 or 3