(1)

 

Input Breaker: Trips to protect utility power from a BBS short circuit. 

(2)

 

Output Breaker: Trips to protect the BBS from a load short circuit. 

(3)

 

Inverter Run Time Meter: Tells the total time the system has operated from 
batteries since the meter was reset. 

(4)

 

Meter Reset Button – Run Time Meter: Push to reset the inverter run time 
meter. 

(5)

 

Meter Reset Button – Number of Outages: Push to reset the inverter 
Number of Outages Meter. 

(6)

 

Number of Outages Meter: Tells the number of times the system has 
operated from batteries since the meter was reset. 

(7)

 

Battery Charger On: The green LED lights only when external AC power is 
present to indicate that the battery charging is engaged. 

(8)

 

Battery Charger Full: The green LED lights only when external AC power is 
present to indicate that batteries are fully charged. 

(9)

 

Check Battery: Yellow LED indicates a problem in the batteries or the battery 
cable. 

(10)

 

Relay A – On Batt: Green LED lights to indicate that the BBS is in Inverter 
mode. 

(11)

 

Relay – B – Low Batt: Green LED lights when the system is in Inverter mode 
and the useful battery capacity remaining is at the reference level chosen by 
user (40% in most applications). 

(12)

 

Relay – C – 2 Hr. Time: Lights only to indicate that the BBS has been in 
Inverter mode for more than two hours. 

(13)

 

Transfer Relay Connector: Two-pin connector connects to the 30ATR or 
CMBPS-30ATR to drive the 30 amps relay. 

(14)

 

Temp. Comp. Sense Wire: Three-pin connector connects to a 9ft extension 
wire to the negative battery post. 

(15)

 

Battery Connector Cable: Enables fast connection to batteries, Red (+) and 
Black (-) marks. 

(16)

 

BBS AC Receptacle Cord: Connects to the 30ATR or CMBPS-30ATR AC plug 
item 33 in Figure 2 page 7. 

(17)

 

BBS AC Connector Plug: Connects to the 30ATR or CMBPS-30ATR receptacle 
cord item 28 in Figure 2 page 7. 

(18)

 

Inverter On: Green LED lights only if the power switch has been set to “On” to 
indicate that the DC to AC inverter is on. 

(19)

 

Inverter – Shutdown – Low Batt: Red LED lights to indicate that the battery 
voltage has dropped to 21VDC and will shutdown in five seconds due to a low 
voltage condition. 

(20)

 

Inverter – Shutdown – Overload: Red LED lights to indicate that the power 
demand by the load is larger than the power the BBS can deliver. The inverter 
will shutdown in five seconds due to an overload condition. 

(21)

 

Inverter – Shutdown – High Temp: Red LED lights to indicate that the 
internal electronic circuit temperature has exceeded the maximum operating 
temperature limit. The inverter will shutdown in five seconds due to a high 
temperature condition. 

(22)

 

Power On/Off Switch: Turns the inverter “On” or “Off” and activates or 
deactivates the dry relay contacts as well. 

Содержание Dimensions ADI-24J11

Страница 1: ...1 LED Signal Battery Backup System Installation Operation and Maintenance Manual ADI 24J11 Form 121984D August 2008...

Страница 2: ...nts 8 4 2 Recommended Useful Tools for Installation 8 4 3 Mounting the BBS 9 4 4 Wiring the BBS 13 4 5 Dry Relay Contact Wiring 15 5 0 Adjustments 17 5 1 Remaining Battery Capacity Adjustment 17 6 0 C...

Страница 3: ...BBS should not be installed in a zero clearance enclosure Damage to the BBS will occur if correct polarity is not observed when installing the DC input cables Damage to the BBS will occur if an extern...

Страница 4: ...ery shutdown at 21 VDC In line battery cable fuse Remote temperature sense cable Temperature compensated battery charging system shuts off over 50 C 122 F Communication RS232 Communication port provid...

Страница 5: ...Physical Description Section 3 3 1 BBS Physical Description FIGURE 1 BBS Module model ADI 24J11 physical description front and rear view 17 1 15 2 3 23 24 25 26 27 14 13 4 5 6 9 10 12 11 7 8 16 18 19...

Страница 6: ...has been in Inverter mode for more than two hours 13 Transfer Relay Connector Two pin connector connects to the 30ATR or CMBPS 30ATR to drive the 30 amps relay 14 Temp Comp Sense Wire Three pin connec...

Страница 7: ...description 28 AC Outlet Cord Connects to item 17 on Figure 1 page 5 29 Indicator Light Lights to indicate the switch is in the bypass mode 30 Terminal Connector Board AC Wiring connector board 31 Byp...

Страница 8: ...case Used on standard applications Washers 250275 and Screws 250274 are included 1 12 VDC 79 AH Group 24 AGM batteries 390003 or 12 VDC 105 AH group 31 batteries 390006 are available One quick connec...

Страница 9: ...BBS is firm and secure FIGURE 3 BBS Module footprint 4 3 2 Mounting the Manual Bypass Switch 30A Transfer Relay Open Frame 511016 1 a Locate a secure and appropriate cabinet shelf as shown in figure 4...

Страница 10: ...cting the BBS incorrectly to the battery will cause damage that is not covered under warranty a Place two batteries on each shelf next to each other b Connect the red wire to the positive post of the...

Страница 11: ...11 FIGURE 8 Absorbent Glass Mat AGM battery and quick connector battery cable Negative Black wire Positive Red wire Anderson Connector Quick Connector 80 Amp Fuse 12 VDC Battery...

Страница 12: ...12 FIGURE 7 BBS components mounted in a Stand Alone Cabinet Batteries ADI 24J11 CMBPS 30ATR Cabinet door...

Страница 13: ...e 6 foot long 10 gauge wires that are supplied for all connections between the controller terminal block and the combined Manual Bypass Switch 30A Transfer Relay Use the existing utility feed wire whe...

Страница 14: ...MBPS and 30ATR 30ATR 451036 A C NEU GRD A C In Out MBPS 511015 Utility To From Hot Input Relay Relay Out On Off AC In AC Out White Green Neutral Ground Blk Transfer relay 2 pin connector NEU Neutral...

Страница 15: ...for Alarm reporting on the Alarm input that was chosen in line a above 4 5 2 Wiring Recommendations Low Batt Relay B Low Batt Relay B may also be used as another Alarm function via Controller input o...

Страница 16: ...ash wiring configuration On Batt Relay A Low Batt Relay B Timer Relay C Connector Option 611241 Black Red White Green Orange Blue Brown Yellow Violet NO C NC NO C NC NO C NC NO Normally open C Common...

Страница 17: ...lash mode wiring is shown on Figure 13 5 1 2 Adjusting the Relay B Low Batt potentiometer Note Potentiometer Position A is fully counterclockwise CCW position E is fully clockwise CW The values in Tab...

Страница 18: ...ppears in Figure 11 When all setup has been completed this will be the HyperTerminal file name that can be accessed without having to re initialize the setting 3 The Connect To window shown in Figure...

Страница 19: ...19 FIGURE 14 FIGURE 15 FIGURE 16 FIGURE 17 FIGURE 11 FIGURE 12 FIGURE 13...

Страница 20: ...the BBS When finished click the Start button The communication session will now be logged The file will be saved automatically upon exit of HyperTerminal 6 2 3 Other Terminal Emulation Setups If anoth...

Страница 21: ...led 7 Batt Voltage Displays the current battery voltage 8 Batt Full Indicates that the battery bank is fully charged 9 Check Batt Indicates a problem with the batteries or the charger 10 Low Batt Rela...

Страница 22: ...Outage The BBS has been in backup mode for 2 hours Protective shutdown The BBS reached the low voltage shutdown level and shutdown to prevent deep discharge Power Up the unit has been turned on after...

Страница 23: ...was designed to supply full backup power within the BBS rating No dry relay wiring connection is needed 1 2 Red Flash Mode Operation The BBS can operate in Red Flash Mode by wiring the appropriate dr...

Страница 24: ...100 amp hour battery will produce five amps for twenty hours before it is exhausted AGM VRLA Absorbed Glass Mat Valve Regulated Lead Acid are maintenance free batteries The liquid electrolytes of AGM...

Страница 25: ...C LIGHT CONTROLLER DIMENSIONS BBS MODULE DC Dry Relay Contact AC AC AC AC CMBPS 30ATR Replaces both items Windows based PC AC Alternate Current DC Direct Current 30ATR 30 amp Automatic Transfer Relay...

Страница 26: ...structed in section 4 4 1 page 13 to ensure proper battery charging 7 2 3 Turning the Inverter On or Off To activate the inverter set the switch on the front of the BBS module to the On position the g...

Страница 27: ...tery Maintenance The BBS uses sealed maintenance free batteries Proper charging and limited cycling along with a proper battery environment will ensure a long battery life Servicing of batteries shoul...

Страница 28: ...able Perform the following troubleshooting steps Set the MBPS to Bypass Mode Set the BBS module power switch to Off Unplug the female and male connector cords coming out from the 30ATR or CMBPS 30ATR...

Страница 29: ...ar or the inverter will shut off Remove the short circuit or excessive load from the output and then switch the inverter off then on If the condition persists call Dimensions 4 High Temp Red LED Indic...

Страница 30: ...or a shorted or defective battery Make sure there is no other source of battery charging The BBS module is in good shape Troubleshoot the 30ATR and MBPS or the CMBPS 30ATR before putting the BBS modul...

Страница 31: ...0060 Fan 290003 Battery conductance tester 295003 Digital meter Hour 295004 Digital meter Counter 390003 AGM Battery with handle 12VDC 79AH 390006 AGM Battery with handle 12VDC 105AH 430013 Circuit Br...

Страница 32: ...3 Wiring diagram including CMBPS 30ATR 120 VAC 60 Hz AC Input Traffic Light Controller Dry relay contact connector Optional 2 pin connector Anderson Connector Fuse Temperature Compensated Cable 12 VDC...

Страница 33: ...rrants to the original purchaser for use that the goods or any component thereof manufactured by Dimensions will be free from defects in workmanship for a period of 5 years from the date of purchase p...

Отзывы: