27
Maintenance & Troubleshooting Section 8
To prevent current being withdrawn from the batteries that results in battery
damage the inverter unit must be switched “Off” and the batteries must be
disconnected from the inverter at the Anderson connector if the Manual Bypass
Switch is in the “Bypass Mode” position.
8.1
Preventive Maintenance:
8.1.1 BBS Module Maintenance:
The BBS module was designed to be
maintenance-free. There are no serviceable parts inside the unit.
It is recommended to do a cleaning routine maintenance as follows:
•
Clean the cover of the BBS as needed using a damp cloth or nonabrasive cleanser.
Do not use ACETONE-BASE cleaning solutions. Keep cleaning solutions
out of the electrical receptacles on this device.
8.1.2 Battery Maintenance:
The BBS uses sealed maintenance-free batteries.
Proper charging and limited cycling along with a proper battery environment will ensure
a long battery life.
Servicing of batteries should be performed or supervised by authorized
personnel at least four times a year.
A battery can present a risk of electrical shock and high short circuit
current.
•
Clean and tighten battery connections.
•
All battery connections should be examined and checked for corrosion.
•
Replace batteries when conductance tests indicate 30% to 40% deterioration from
the original value. Use a battery conductance tester, Dimensions part number
290003.
•
When replacing batteries, use the same model number and type batteries. Batteries
should be replaced in complete sets.
•
Before proceeding with installation, review battery system drawings and assembly
according to provided instructions.
•
Normal battery operating temperatures are between 68°F (20°C) and 77°F (25°C).