SENS IQ Technical Manual
10
Service Hotline: 1.800.742.2326
1.303.678.7500
Table 1: AC Input Current and AC/DC Circuit Breaker Current Ratings
Charger
Model
Rated AC Input Current
*AC Input Branch Circuit Breaker
Ratings
Charger Input Breaker
Current Ratings
Charger
Output
Breaker
Current
Ratings
480V
60Hz
(8)
120/208/240V
50/60Hz (P),
60Hz (T)
400V
50/60Hz
(V)
480V
60Hz
(8)
120V
50/60Hz
(P), 60Hz
(T)
400V
50/60Hz
(V)
480V
60Hz
(8)
120/208/240V
50/60Hz (P),
60Hz (T)
400V
50/60Hz
(V)
Q012-012 0.8
3.2/1.8/1.6
1.0
15 10 or 15
15
15
10 or 15
15
15
Q012-016 1.0
4.2/2.4/2.1
1.2
15 10 or 15
15
15
10 or 15
15
20
Q012-025 1.6
6.3/3.6/3.1
1.9
15 10 or 15
15
15
10 or 15
15
35
Q012-035 2.1
8.5/4.9/4.3
2.6
15
15
15
15
15
15
45
Q012-050 3.1
13/7.2/6.3
3.8
15
20
15
15
20
15
70
Q024-006 0.7
2.9/1.7/1.5
0.9
15 10 or 15
15
15
10 or 15
15
10
Q024-012 1.4
5.6/3.2/2.8
1.7
15 10 or 15
15
15
10 or 15
15
15
Q024-016 1.8
7.4/4.3/3.7
2.2
15 10 or 15
15
15
10 or 15
15
20
Q024-025 2.9
12/6.7/5.8
3.5
15
15
15
15
15
15
35
Q024-035 4.0
16/9.1/7.9
4.7
15
20
15
15
20
15
45
Q024-050 5.6
23/13/11
6.8
15
30
15
15
30
15
70
Q048-006 1.3
5.2/3.0/2.6
1.6
15 10 or 15
15
15
10 or 15
15
10
Q048-012 2.6
10/5.9/5.1
3.1
15
15
15
15
15
15
15
Q048-016 3.3
13/7.7/6.7
4.0
15
20
15
15
20
15
20
Q048-025 5.2
21/12/10
6.2
15
30
15
15
30
15
35
Q048-035 7.1
29/17/14
8.6
15
40
15
15
40
15
45
Q048-050 10
40/23/20
12
15
50
15
15
50
15
70
Q120-006 3.1
12/7.0/6.1
3.7
15
15
15
15
15
15
15
Q120-012 5.9
24/14/12
7.0
15
30
15
15
30
15
15
Q120-016 7.8
31/18/16
9.4
15
40
15
15
40
15
20
Q120-025 12
47/27/24
14
15
60
20
15
60
20
35
Q240-006 5.9
24/14/12
7.0
15
30
15
15
30
15
15
Q240-012 11
44/26/23
14
15
60
20
15
60
20
15
208V
50/60Hz
(P), 60Hz
(T)
240V
50/60Hz
(P), 60Hz
(T)
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
15
10 or 15
20
15
10 or 15 10 or 15
10 or 15 10 or 15
10 or 15 10 or 15
15
15
25
20
30
25
10 or 15 10 or 15
20
15
25
20
35
30
20
15
35
30
Wire Gauge
Min
Max
240 VAC,
24A
# 14 Cu or Al
#2 Cu or Al
240 VAC (All)
# 14 Cu, #12 Al #2 Cu, #4 Al
Rated Charger Input
240 VAC, 60 Hz,
24A
# 14 Cu or Al
#2 Cu or Al
240 VAC, 50/60 Hz,
24A
# 14 Cu, #12 Al # 1/0 Cu or Al
Table 2: AC Input Wire Gauge Ratings
*User must incorporate a branch circuit breaker external to the charger to provide a mode of disconnection from the supply mains.
NOTE:
Table 2 represents only the physical capabilities of the terminals. In addition
to the physical limitations, conductors must be electrically adequate per local
electrical safety regulations (such as the National Electrical Code
®
).
NOTE:
Breakers designated as “10 or 15” indicate a 10 Amp breaker for input code
T and a 15 Amp breaker for input code P.