CONNECTION OF THE DEVICES TO A NETWORK (ONLY R-32DIDO MODEL)
CONNECTION OF THE DEVICE TO A NETWORK
The factory configuration of the IP address is:
Static address: 192.168.90.101
Therefore, multiple devices must not be inserted on the same network with the same static IP.
If you want to connect multiple devices on the same network, you need to change the IP address configuration
using the Easy Setup 2 software.
ATTENTION!
DO NOT CONNECT 2 OR MORE FACTORY-CONFIGURED DEVICES ON THE SAME NETWORK, OR THE
ETHERNET INTERFACE WILL NOT WORK
(192.168.90.101 IP ADDRESS CONFLICT)
If the addressing mode with DHCP is activated and an IP address is not received within 1 minute, the device will
set an IP address with a fixed error:
169.254.x.y
Where x.y are the last two values of the MAC ADDRESS.
This way it is possible to install more I/O of the R series and then configure the IP with the Easy Setup 2
software even on networks without a DHCP server.
USING EASY SETUP 2 TO CONFIGURE DEVICES
The Easy Setup 2 software allows:
▪
Configuring R series devices via the USB port
▪
Searching and configuring Seneca R-series devices on an Ethernet network
In the case of a first installation we recommend following these steps:
1)
Install the Easy Setup 2 software
2)
Power and connect the device to the PC via the USB port