SUPPORTED MODBUS COMMUNICATION PROTOCOLS (MODEL R-32DIDO
ONLY)
The Modbus communication protocols supported are:
▪
Modbus RTU Slave (from the RS485 and USB ports)
▪
Modbus TCP-IP Server (from Ethernet ports) 8 clients max
For more information on these protocols, see the website:
http://www.modbus.org/specs.php
SUPPORTED MODBUS FUNCTION CODES
The following Modbus functions are supported:
▪
Read Holding Register
(function 3)
▪
Read Coil Status
(function 1)
▪
Write Coil
(function 5)
▪
Write Multiple Coil
(function 15)
▪
Write Single Register
(function 6)
▪
Write Multiple Registers
(function 16)
ATTENTION!
All 32-bit values are contained in 2 consecutive registers
ATTENTION!
Any registers with RW* (in flash memory) can be written up to 10000 times
The PLC/Master Modbus programmer must not exceed this limit