User Manual
R-32DIDO SERIES
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
Doc: MI-00576-2-EN
Page 14
DEVICE CONFIGURATION
To configure the device, access the web server and select the section you are interested in.
After a modification to the configuration has been made, the changes must be confirmed with the "
APPLY
"
button and the device will restart autonomously.
The
Reboot
button reboots the device (not necessary in the event of a configuration change).
The
Default
button returns all the page parameters to the default settings.
SETUP SECTION
DHCP (ETH) (default: Disabled)
Sets the DHCP client to get an IP address automatically.
IP ADDRESS STATIC (ETH) (
default: 192.168.90.101
)
Sets the device static address. Careful not to enter devices with the same IP address into the same network.
IP MASK STATIC (ETH) (default: 255.255.255.0)
Sets the mask for the IP network.
GATEWAY ADDRESS STATIC (ETH) (default: 192.168.90.1)
Sets the gateway address.
PROTECT CONFIGURATION (default: Disabled)
Allows you to enable or disable password protection for reading and writing the configuration (including the IP
address) using the Easy Setup 2 software or Seneca Discovery Tool. The password is the same one that allows
accessing the web server.
ATTENTION!
IF THE CONFIGURATION PROTECTION IS ENABLED IT WILL BE IMPOSSIBLE TO READ/WRITE THE
CONFIGURATION OF THE DEVICE WITHOUT KNOWING THE PASSWORD.
IN THE EVENT OF LOSING THE PASSWORD IT WILL BE POSSIBLE TO RETURN THE DEVICE TO THE
FACTORY CONFIGURATION (SEE CHAPTER 7)
MODBUS SERVER PORT (ETH) (default: 502)
Sets the communication port for the Modbus TCP-IP server.
MODBUS SERVER STATION ADDRESS (ETH) (default: 1)
Active only if Modbus Passthrough is also active, it sets the station address of the modbus TCP-IP server.