DIGITAL I/O SETUP SECTION
This section allows the configuration of the digital I/Os present in the device.
DIGITAL I/O MODE (default Input)
Selects whether the selected input will work as an input or output.
DIGITAL INPUT NORMALLY HIGH/LOW (default Normally Low)
If selected as digital input, it configures whether the input is normally high or low.
DIGITAL OUTPUT NORMALLY STATE (default Normally Open)
If selected as digital output, it configures whether the output is normally open or closed.
DIGITAL OUTPUT WATCHDOG (default Disabled)
If selected as digital output, it sets the output watchdog mode.
If “Disabled”, it disables the watchdog function for the selected output.
If "Enabled on Modbus Communication" the output goes into "Watchdog state" if there has been no generic
Modbus communication within the set time.
If "Enabled on Modbus Digital Output Writing" the output goes into "Watchdog state" if there has been no writing
of the output within the set time.
DIGITAL OUTPUT WATCHDOG STATE (default Open)
Sets the value that the digital output must adopt if the watchdog has been triggered.
DIGITAL OUTPUT WATCHDOG TIMEOUT [s] (default 100s)
Represents the watchdog time of the digital output in seconds.
SETUP COUNTERS SECTION
COUNTERS FILTER [ms] (default 0)
Sets the value in [ms] for filtering all the counters connected to the inputs.