2.1 Rack Installation
The OmniHub CMP100 is designed to be mounted in a standard 19” rack. It takes 480mm
x 177mm x 345mm (W x H x D) or 4RU of rack space. To install it into a rack, please use
the following steps:
•
Determine the desired position in the rack for the CMP100. Make sure that the air
intake on the top of the unit and the exhausts on the back of the unit will not be
blocked.
•
Install the brackets at desired position if there’s no supporting plate in the rack.
•
Insert the rack mount clips into place over the mounting holes in the rack.
•
Slide the CMP100 into the position in the rack.
•
Secure the chassis to the rack by installing the four supplied screws through the
front mounting holes and tightening.
2.2 AC Power Connection
The Dual Redundant option allows the OmniHub CMP100 to be powered by two separate
supplies either operating 110V or 220V systems. The power supply will automatically
detect the system it is connected to. To hook up the power use the following steps:
•
Locate the power cords that are included. Please only use the supplied 3-prong
power connector or one with equal specifications. NEVER tamper with or remove
the grounding pin. This could cause damage to CMP100, personnel, or property.
•
Plug the female end of the power cords into the front of the unit.
•
Locate a protected outlet to plug the male ends of the power cables into.