pg. 16
If solid concrete or brick wall, drill
½
inch diameter holes to a depth of 4 inches for the anchor bolts
provided. For walls other than concrete, solid block or brick, use fasteners appropriate for material.
Now, run conduit up to wire wall hole location previously marked on the wall. Run the wires through
this conduit up to wire wall hole location with at least 18” (+wall thickness) free wire. See illustration
for clarity.
NOTE
:
If the conduit is run on the same side of the wall as the charging station the wires are then
run through the opening on the side of the Wall/Pole Mount Bracket Post.