Self Climat DN 50, DN 80 and DN 100 type overfill prevention devices all conform to the Directive
2014/34/EU.
This equipment, suitable for use in group IIB explosive atmospheres, is constructed according to the following
European standards :
-
EN 13616-1 : 2016 (harmonized standard)
-
EN 13463-1 : 2001
-
EN 13463-5 : 2003
The EN 13463-1: 2001 and EN 13463-5: 2003 standards are no longer harmonized but the conformity of the
material is not impacted by the substantial modifications of the EN 13463-1: 2009, EN 13463-5: 2011,
EN 80079-36: 2016 and EN 80079-37: 2016 standards.
DN 50
DN 80
DN 100
Self Climat
77200 TORCY
FRANCE
Overfill prevention device
Type DN50
Subtype A2
0080
II 1 G c IIB T6
T
amb.
: -25°C to +60°C
INERIS 07ATEX0037
Self Climat
77200 TORCY
FRANCE
Overfill prevention device
Type DN80
Subtype A2
0080
II 1 G c IIB T6
T
amb.
: -25°C to +60°C
INERIS 07ATEX0037
Self Climat
77200 TORCY FRANCE
Overfill prevention device
Type DN100
Subtype A2
0080
II 1 G c IIB T6
T
amb.
: -25°C to +60°C
INERIS 07ATEX0037
The
Self Climat
overfill prevention device is a mechanical safety device placed on the filling tube inside the
liquid
storage tank.
The purpose of this «completely safe overflow prevention device» is to reduce environmental risks, water
pollution risks and all fire or explosion risks that could arise while filling liquid petroleum fuel storage tanks.
It is essential to verify the compatibility between the overfill prevention device and the liquid stored in the tank,
as the characteristics of the liquid determine the type of overfill prevention device to be installed.
The
Self Climat
technical dept has all the information necessary to advise installing technicians in their choices.
OVERFILL PREVENTION DEVICE
Designation
Pump flow
DN
Working
pressure
Working
temperature*
Max. fluid
temperature
OPD - Type DN 50
40 m
3
/h
50
6 bar
-25°C à +60°C
+80°C
OPD - Type DN 80
60 m
3
/h
80
8 bar
-25°C à +60°C
+80°C
OPD - Type DN 100
84 m
3
/h
100
8 bar
-25°C à +60°C
+80°C
* The temperature of the equipment depends on the temperature of the fluid
This device is designed for liquid petroleum fuels: heating oil, diesel fuel, gasoline, lead-free gasoline
and leaded gasoline.
I) MARKING
II) GENERAL SPECIFICATIONS