INSTRUCTION MANUAL CODE 80152 REV E DEC 2019 (They can be modified without notice)
Page: 29
J
.P. SELECTA s.a.u.
Ctra. NII Km 585.1 Abrera 08630 (Barcelona) España
Tel 34 937 700 877 Fax 34 937 702 362
e-mail: [email protected] - website: www.grupo-selecta.com
RS-232 INSTRUCTIONS FOR VACIOTEM T AND VACIOTEM TV OVENS
Vaciotem T / Vaciotem TV
PVT?
Get probe temperature PV (Point value):
Command
:
#01PVT?KK<CR><LF>
Answer
:
#01+000KK<CR><LF>
Vaciotem TV
PVP?
Get pressure value
Command
:
#01PVP?KK<CR><LF>
Answer
:
#010000KK<CR><LF>
Vaciotem T / Vaciotem TV
SVT?
Get Set point temperature:
Command
:
#01SVT?KK<CR><LF>
Answer
:
#01+000KK<CR><LF>
SVT
Set point temperature
Command
:
#01SVT<BL>+000KK<CR><LF>
Answer
:
#01OKKK<CR><LF>
Vaciotem TV
SVP?
Get Set point temperature:
Command
:
#01SVP?KK<CR><LF>
Answer
:
#010000KK<CR><LF>
SVP
Set point temperature
Command
:
#01SVP<BL>+0000KK<CR><LF>
Answer
:
#01OKKK<CR><LF>
Vaciotem T / Vaciotem TV
RUN?
Get status variable
Command
:
#01RUN?KK<CR><LF>
Answer
:
Temperature stop: #01STPTKK<CR><LF>
Pressure stop: #01STPPKK<CR><LF>
Temperature run: #01RUNTKK<CR><LF>
Pressure run: #01RUNPKK<CR><LF>
Alarm status: #01ALARKK<CR><LF>
Standby time: #01STBYKK<CR><LF>
Model Vaciotem TV gives compound answers. For exemple:
#01STPT<BL>STPPKK<CR><LF>
Vaciotem TV
RUN
Starts run:
Command
:
#01RUNKK<CR><LF>
Answer
:
#01OKKK<CR><LF>
Vaciotem T / Vaciotem TV
RUNT
Starts temperature control:
Command
:
#01RUNTKK<CR><LF>
Answer
:
#01OKKK<CR><LF>