SEG Electronics GmbH
Manual MRG3
82
DOK-TD-MRG3, Rev. D
7.8.7 Residual voltage protection
Setting range
Step
Tolerance
U
0
>
e-n: 1 - 86%
1:1: 1 - 150 %
1
(1...150)
2% of the set value or 1 %
from U
N
U
0
>
Warning or tripping of the
I
0
> element
trip; warn
tU
0
>
0.1...50 s (EXIT)
0.02
(0.04...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10)
0.5
(10...20)
1.0
(20...50)
2.0
(50...100)
5.0
(100...200)
10.0
(200...300)
1% or
20ms
U
0
>>
e-n: 1 - 70 %
1:1: 1 - 120 %
1
(1...120)
2% of the set value or 1 %
from U
N
tU
0
>>
0.04...300 s (EXIT)
0.02
(0.04...1.0)
0.05
(1.0...2.0)
0.1
(2.0...5.0)
0.2
(5.0...8.5)
0.5
(10...20)
1.0
(20...50)
2.0
(50...100)
5.0
(100...200)
10.0
(200...300)
1% or
20ms
Table 7.6: Residual voltage protection
7.8.8 CB failure protection
LED
Setting range
Step
(range)
Tolerance
tCBFP>
0.1...2.00s (EXIT)
0.02
(0.10...1.00)
0.05
(1.00...2.00)
Table 7.7: CB failure protection
7.8.9 Interface parameter
Function
Parameter
Modbus protocol
RS485 Open Data Protocol
RS
Slave address
1 - 32
1 - 32
RS
Baud-Rate*
2400, 4800, 9600
9600 (fixed)
RS
Parity*
even, odd, no
„even Parity“ (fixed)
Table 7.8: Interface parameter
* only Modbus protocol