5.8 Fault recorder
5.8.1 Adjustment of the fault recorder
The MRG3 is equipped with a fault recorder (see chapter 4.8. Three parameters can be adjusted.
5.8.2 Number of the fault recordings
The max. recording time is 20 s at 50 Hz or 16,66 s at 60 Hz.
The number of max. recordings requested has to be determined in advance. There is a choice of 1*
2, 3* 4 and 7* 8 recordings and dependent on this the duration of the individual fault recordings is
defined, i.e.
Number of recordings
Rated frequency
Unit type
1*
1*/2
3*/4
7*/8
20.00 s 10.00 s
5.00 s
2.50 s
50 Hz
MRG3;
MRG3-U0
16.66 s
8.33 s
4.16 s
2.08 s
60 Hz
10.00 s
5.00 s
2.50 s
1.25 s
50 Hz
MRG3-I;
MRG3-IU0;
MRG3-IE;
MRG3-IER
8.33 s
4.16 s
2.08 s
1.04 s
60 Hz
Table 5.3: Fault record duration
*The oldest record will be overwritten in case that the fault recorder is triggered although there is no
more memory available.
If the respective partition was defined as not being over writeable and the maximal number of rec-
orded disturbance events was assigned, the LED FR starts flashing (refer to chapters 4.8
und5.10.10).
5.8.3 Adjustment of trigger occurrences
There is a choice between four different occurrences:
P_UP (Pickups)
Storage is initiated after recognition of a general activation.
TRIP
Storage is initiated after a trip has occurred.
A_PI (After Pickup)
Storage is initiated after the last activation threshold was fallen
short of (recognizes e.g. circuit breaker failure protection).
TEST
Storing is activated by simultaneous actuation of the keys <+> and <->.
During the recording time the display s
hows “Test”.
5.8.4 Pre-trigger time
By the time T
pre
it is determined which period of time prior to the trigger occurrence should be
stored as well. It is possible to adjust a time between 0.05s and 1,25; 2,5 und 5s. With keys <+>
and <-> the values can be changed and with <ENTER> be saved.