5.5.4 Reset mode for all tripping characteristics in the phase current path
To ensure tripping, even with recurring fault pulses shorter than the set trip delay, the reset mode
for in-verse time tripping characteristics can be switched over. If the adjustment I + 1 + > = 60s,
the tripping time is only reset after 60 s of faultless condition.
This function is not available if I + 1 + > = 0. With fault current cease the trip delay is reset immedi-
ately and started again at recurring fault current.
5.5.5 Pick-up value for high set element
T
he current setting value of this parameter is related to the generator’s rated current of the relay
and is indicated in %.
When the current setting for high set element is set out of range ("EXIT" appears on the display),
the high set element of the over current relay is blocked.
The high set element can be blocked via terminals E8/D8 if the corresponding blocking parameter
is set to bloc (refer to chapter 5.9.1).
5.5.6 Trip delay for high set element
Independent from the chosen tripping characteristic for I>, the high set element I>> has always a
definite-time tripping characteristic. An indication value in seconds appears on the display.