HUBBELL TPDS, TPDL 

Temporary branch power distribution unit  

with ground fault protection for personnel 

 

 

 

 

 

          Installation and Operating Instructions 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
SPECIFICATION 

These installation and operating instructions 
apply to the following temporary power 
branch distribution system components.  
Do not discard these instructions, save for 
future reference. 
 

PORTABLE POWER DISTRIBUTION 

UNITS 

All units are rated 50 amps,125/250 VAC, 
Single Phase, 5 milliampere leakage current 
trip level. Downstream protection is not 
provided through the 50 amp outlet. The 20 
amp, 120 volt outlets are individually 
protected by circuit breakers and GFCI 
circuit modules. 
 

Model 

Number 

20 Amp 

Receptacle 

TPDL 

TWIST LOCK 

TPDS 

STRAIGHT BLADE 

 

INTRODUCTION 

Hubbell temporary power branch distribution 
units equipped with GFCI products, will 
protect you from shock hazards resulting 
from ground faults. 
Ground faults are current leaks and can 
result in electric shock. Currents of only 
60/1000 of an ampere can be fatal. The 
GFCI protection provided by Hubbell 
temporary power branch distribution units 
significantly minimizes shock hazards. 
Hubbell temporary power branch distribution 
products, which are listed by Underwriters 
Laboratories as Class A, Group I 
interrupters, respond to fault currents as low 
as 5 milliamperes, and will shut off the 
current within 1/40th of a second. 
 
 

 
 
The temporary power branch distribution unit is 
designed to provide protection against electrical 
shock hazards due to line-to-ground faults. 
Although the GFCI Module does not limit the 
magnitude of the fault current, and therefore 
cannot prevent electric shock, it does limit the 
duration of the shock to a period considered safe 
for normally healthy persons.  
GFCI Modules will provide protection against 
ground faults only. They will not protect against 
overloads or short circuits. There is no known 
device that will guard against the electrical shock 
hazard resulting from contact with both the “hot” 
and neutral wires of the electric circuit. 

ELECTRICITY IS DANGEROUS. 
EVEN WHEN SAFETY DEVICES ARE 
PRESENT, HANDLE WITH CARE AND USE 
REASONABLE CAUTION. 
 
LET CAUTION PREVAIL 

The Hubbell temporary power branch distribution 
unit is designed to be used on a grounded 
electrical supply system. It will not operate when 
supplied from a power source which is not 
grounded. Over-current protection of the proper 
rating, according to the National Electrical Code, 
Article 240, must be used on the supply circuit 
feeding the temporary power branch distribution 
units. 
 

TEST PROCEDURE 
All Models 

Connect the temporary power branch distribution 
unit to an appropriate power source.

 

CAUTION 
 

•  Power is immediately available at the 50 

       amp outlet when the source is energized 
      on all models.   
1. Verify all circuit breakers are in the “on”    
  position.

 

 

 

 

 

Wiring Device-Kellems 
Hubbell Incorporated (Delaware) 
185 Plains Road 
Milford, CT 06460-8897 
(203) 882-4800

 

PD2216          

PRINTED IN U.S.A.            

12/06

 

 