Protection parameters: Phase and earth fault protection
Relay type
Default set-
tings
Actual
settings
Symbol LED
Function
Unit
M
RG
3
M
RG
3
-I
M
RG
3
-U0
M
RG
3
-IE
M
RG
3
-IU0
M
RG
3
-IER
Set 1
Set 2
Set1
Set 2
I>
I+1+>
Pickup value for phase
over current element
%
X
X X X 20
I> Char
I+1
Tripping characteristic for
phase over current ele-
ment
X
X X X DEFT
tI>
I+1+>+t>
Tripping time (factor) for
phase over current ele-
ment
(s)
X
X X X 0.04
I>_Rese
t
I+1+>+t>
Reset mode for phase
over current element
X
X X X 0s
I>>
I+2+>
Pickup value for fast
phase
– short-circuit trip-
ping
%
X
X X X 50
tI>>
I+2+>+t>
Tripping value of the fast
phase short-circuit tripping
s
X
X X X 0.04
U
0
>
U
0
+1
Warning/tripping of the
U
0
> element
X
X
warn
U0>+t>
U0+1+>+t>
Tripping delay for the 1
st
residual voltage element
s
X
X
0.1
U0>>
U0+2+>
Pickup value for the 2
nd
residual voltage element
%
X
X
10
U0>>+t> U0+2+>+t>
Tripping delay for the 2
nd
residual voltage element
s
X
X
0.1
I
E
>
I
E
+1
Warning/tripping of the I
E
>
element
X
X warn
I
E
>
I
E
+1+>
Pickup value for earth
over current
%
X
X 1
I
E
> Char I
E
+1
Tripping characteristic for
earth over current element
X
DEFT
tI
E
>
I
E
+1+>+t>
Tripping time (factor) for
the earth over current el-
ement
(s)
X
0.04
tI
E
>
I
E
+1+>+t>+
Tripping time (factor) for
earth over-current element
in forward direction
(s)
X
X 0.1
tI
E
>
I
E
+1+>+t>+
Tripping time for earth
over current element
backward direction
(s)
X 0.1
I
E
>_Res
et
I+1+>+t>
Reset mode for earth over
current element
X
0s
I
E
>>
I
E
+2+>
Pickup value for fast earth
short circuit tripping
%
X
X 1
tI
E
>>
I
E
+2+>+t>+
Tripping time for the earth
short-circuit tripping
s
X
0.04
tI
E
>>
I
E
+2+>+t>+
Tripping value of fast
earth short circuit trip-
ping/forward direction
s
X
X 0.1
tI
E
>>
I
E
+1+>+t>+
Tripping value of fast
earth short circuit trip-
ping/backward direction
s
X 0.1
SIN/CO
S
I
E
+1+2+>
Evaluation for isolat-
ed/compensated grids
X SIN
CB+t>
CB+t>
Tripping time for CB failure
protection
s
X
X X X EXIT